ES-0884 Rev.8

10ABS

High-density Signal Conditioners 10-RACK

ANALOG BACKUP SWITCHER

Functions & Features
• Changing control from DCS output to manual operation
• Control output selectable by an external switch

Typical Applications
• Enabling manual operation of valves

MODEL: 10ABS–AA–R[1]

ORDERING INFORMATION

• Code number: 10ABS-AA-R[1]
Specify a code from below for [1].
  (e.g. 10ABS-AA-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

INPUT

Current
A: 4 – 20 mA DC

OUTPUT

Current
A: 4 – 20 mA DC

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection 
  Input: M3.5 screw terminals (torque 0.8 N·m) 
  Output: M3.5 screw terminals (torque 0.8 N·m)
  Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input or output to power
Indicator LED: Light turns on during DCS control

INPUT SPECIFICATIONS

Input: control output of the DCS; 4 – 20 mA DC

OUTPUT SPECIFICATIONS

Output: 4 – 20 mA DC
Relay mechanical life: 5 x 107 cycles

INSTALLATION

Current consumption: Approx. 40 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 10BXx
Weight: 150 g (0.33 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or output to power)
1500V AC @1 minute (input or output to ground)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM