ES-0892 Rev.11

10BXA

High-density Signal Conditioners 10-RACK

STANDARD RACK

(with air manifold)
Functions & Features
• Standard 19" rack for I/P transducers (model: 10VP)
• Line power access at the terminal card, supplied via the rear rack bus
• Supply pressure at the manifold plug
• Other 10-Rack signal conditioners are also mountable

MODEL: 10BXA–R[1]

ORDERING INFORMATION

• Code number: 10BXA-R[1]
Specify a code from below for [1].
  (e.g. 10BXA-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
Power supply and signal conditioner side of the main PWB are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Coating: Zn-Cr (black), alumetized steel
Capacity: 16 positions
Connection
Power input: M4 screw terminals
(torque 0.8 N·m)
  Screw terminal: Nickel-plated steel
Pneumatic: Rc 3/8" female (torque ≤ 12 N·m)
  Screw terminal: Nickel-plated brass
Manifold: Aluminium alloy
Isolation: Power to FG

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS/EIA standard rack or angle bracket
Weight: 4.5 kg (9.9 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (power to FG)
Maximum supply pressure: 196 kPa
(2 kgf/cm2, 1.96 bar, 28 psig)

MOUNTING REQUIREMENTS

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)