ES-0893 Rev.15

10BXC

High-density Signal Conditioners 10-RACK

STANDARD RACK

Functions & Features
• Standard 19" rack for 10-RACK signal conditioners
• Line power supplied via the rear rack bus
• Dual-redundant power supply or two independent power sources selectable with AC power supply
• Supply pressure at manifold plug
• Direct interface to various DCS with the rack connector

MODEL: 10BXC-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 10BXC-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 10BXC-12-K2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] FUNCTION

1: Power distribution
2: Power distribution & pressure supply

[2] CONNECTOR

0: None
1: Fujitsu FCN type I/O connector
2: Yokogawa DCS connector (MAC2 dual redundant system use)
3: Nippon Shokubai DCS connector
4: Azbil DCS AI connector
5: Azbil DCS AO connector
6: Azbil DCS AI connector (ELCO connector)
7: Azbil DCS AO connector (ELCO connector)
8: Yokogawa DCS connector (VMx/PM1 dual redundant system use)
E3: Toshiba DCS SAIN1 card use 
    (Panasonic AXM220001 used)
   (DISCONTINUED; replace with code "E3A".)
E3A: Toshiba DCS SAIN1 card supported
     (Omron XG4A-2031 used)
H1: Hitachi DCS connector
H2: Hitachi DCS EX-CDL cable connector
We guarantee the connecting section.

[3] POWER SUPPLY UNIT

AC Power
K: 85 – 132 V AC; single power source
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
K2: 85 – 132 V AC; dual-redundant power supply 
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
KK: 85 – 132 V AC; two independent power sources
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
L: 170 – 264 V AC; single power source
(Operational voltage range 170 – 264 V, 47 – 63 Hz)
L2: 170 – 264 V AC; dual-redundant power supply
(Operational voltage range 170 – 264 V, 47 - 63 Hz)
DC Power
R: 24 V DC; no power supply unit
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
AC/DC Power
KR: 85 – 132 V AC / 24 V DC; two independent power sources
(85 – 132 V, 47 – 63 Hz or 24V ±10 %, ripple 10 %p-p max.)
(Redundant or independent power sources are recommended for long time use without interruption.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
Power supply and signal conditioner side of the main PWB are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Blank filler plate (model: P-101)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Capacity: 16 positions
Connection
Power input: M4 screw terminals (torque 0.8 N·m)
  Screw terminal: Nickel-plated steel
Power alarm: M4 screw terminals (torque 0.8 N·m)
  Screw terminal: Nickel-plated brass
Pneumatic: Rc 3/8" female (torque ≤ 12 N·m)
  Screw terminal: Nickel-plated brass
Manifold: Aluminium alloy
Isolation: I/O connector to alarm output to power to FG
Power alarm output: N.C. contact turns off at power failure or failure of power units. Supplied only with dual-redundant power supply or two independent power sources
Power RUN LED: Light turns on in normal conditions (supplied only with dual-redundant power supply or two independent power sources)

OUTPUT SPECIFICATIONS

Alarm Output
(Supplied only with dual-redundant power supply or two independent power sources)
Rated load: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 750 VA or 60 W
Minimum load: 5 V DC @ 100 mA
Mechanical life: 5 × 106 cycles (rate 180 cycles/min.)

INSTALLATION

Supply pressure: Refer to the data sheet for I/P transducers (power distribution & pressure supply type)
Power consumption
AC: 130 VA min.
DC: 2.5 A min.
Operating temperature: -5 to +55°C (23 to 131°F) 0 to 50°C (32 to 122°F) for AC power
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS or EIA standard rack
Weight
Single power supply w/o power units
:
  3.0 kg (6.6 lb) with DC power type
  3.5 kg (7.7 lb) with AC power type
Dual-redundant or two independent power sources:
  3.5 kg (7.7 lb) with AC/DC power type
  4.0 kg (8.8 lb) with AC/AC power type
Add 2 kg (4.4 lb) for air manifold type.

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (I/O connector to alarm output to power)
1500 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (I/O connector or alarm output to FG, 1000 AC with power input code R)
Maximum supply pressure: 196 kPa
(2 kgf/cm2, 1.96 bar, 28 psig)

MOUNTING REQUIREMENTS

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)