ES-0893 Rev.15
10BXC
High-density Signal Conditioners 10-RACK
STANDARD RACK
Functions & Features
• Standard 19" rack for 10-RACK signal conditioners
• Line power supplied via the rear rack bus
• Dual-redundant power supply or two independent power sources selectable with AC power supply
• Supply pressure at manifold plug
• Direct interface to various DCS with the rack connector
MODEL: 10BXC-[1][2]-[3][4]
ORDERING INFORMATION
• Code number: 10BXC-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. 10BXC-12-K2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] FUNCTION
1
: Power distribution
2
: Power distribution & pressure supply
[2] CONNECTOR
0
: None
1
: Fujitsu FCN type I/O connector
2
: Yokogawa DCS connector (MAC2 dual redundant system use)
3
: Nippon Shokubai DCS connector
4
: Azbil DCS AI connector
5
: Azbil DCS AO connector
6
: Azbil DCS AI connector (ELCO connector)
7
: Azbil DCS AO connector (ELCO connector)
8
: Yokogawa DCS connector (VMx/PM1 dual redundant system use)
E3
: Toshiba DCS SAIN1 card use
(Panasonic AXM220001 used)
(DISCONTINUED; replace with code "E3A".)
E3A
: Toshiba DCS SAIN1 card supported
(Omron XG4A-2031 used)
H1
: Hitachi DCS connector
H2
: Hitachi DCS EX-CDL cable connector
We guarantee the connecting section.
[3] POWER SUPPLY UNIT
AC Power
K
: 85 – 132 V AC; single power source
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
K2
: 85 – 132 V AC; dual-redundant power supply
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
KK
: 85 – 132 V AC; two independent power sources
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
L
: 170 – 264 V AC; single power source
(Operational voltage range 170 – 264 V, 47 – 63 Hz)
L2
: 170 – 264 V AC; dual-redundant power supply
(Operational voltage range 170 – 264 V, 47 - 63 Hz)
DC Power
R
: 24 V DC; no power supply unit
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
AC/DC Power
KR
: 85 – 132 V AC / 24 V DC; two independent power sources
(85 – 132 V, 47 – 63 Hz or 24V ±10 %, ripple 10 %p-p max.)
(Redundant or independent power sources are recommended for long time use without interruption.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
Power supply and signal conditioner side of the main PWB are not coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Blank filler plate (model: P-101)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Capacity
: 16 positions
Connection
•
Power input
: M4 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
•
Power alarm
: M4 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated brass
•
Pneumatic
: Rc 3/8" female (torque ≤ 12 N·m)
Screw terminal
: Nickel-plated brass
Manifold
: Aluminium alloy
Isolation
: I/O connector to alarm output to power to FG
Power alarm output
: N.C. contact turns off at power failure or failure of power units. Supplied only with dual-redundant power supply or two independent power sources
Power RUN LED
: Light turns on in normal conditions (supplied only with dual-redundant power supply or two independent power sources)
OUTPUT SPECIFICATIONS
■
Alarm Output
(Supplied only with dual-redundant power supply or two independent power sources)
Rated load
: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage
: 250 V AC or 125 V DC
Maximum switching power
: 750 VA or 60 W
Minimum load
: 5 V DC @ 100 mA
Mechanical life
: 5 × 10
6
cycles (rate 180 cycles/min.)
INSTALLATION
Supply pressure
: Refer to the data sheet for I/P transducers (power distribution & pressure supply type)
Power consumption
•
AC
: 130 VA min.
•
DC
: 2.5 A min.
Operating temperature
: -5 to +55°C (23 to 131°F) 0 to 50°C (32 to 122°F) for AC power
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: JIS or EIA standard rack
Weight
Single power supply w/o power units
:
3.0 kg (6.6 lb) with DC power type
3.5 kg (7.7 lb) with AC power type
Dual-redundant or two independent power sources
:
3.5 kg (7.7 lb) with AC/DC power type
4.0 kg (8.8 lb) with AC/AC power type
Add 2 kg (4.4 lb) for air manifold type.
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute (I/O connector to alarm output to power)
1500 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (I/O connector or alarm output to FG, 1000 AC with power input code R)
Maximum supply pressure
: 196 kPa
(2 kgf/cm
2
, 1.96 bar, 28 psig)
MOUNTING REQUIREMENTS
CONNECTION DIAGRAM
DIMENSIONS unit: mm (inch)
I/O CONNECTOR PIN ASSIGNMENT