ES-0895 Rev.2
10BXUA
High-density Signal Conditioners 10-RACK
STANDARD RACK
(2 positions, with air manifold)
Functions & Features
• Standard rack for I/P transducers (model: 10VP)
• Line power supplied via the rear rack bus
• Supply pressure at the manifold plug
• Other 10-Rack signal conditioners are also mountable
MODEL: 10BXUA–[1][2]
ORDERING INFORMATION
• Code number: 10BXUA-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. 10BXUA-K/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER SUPPLY UNIT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
Power supply and signal conditioner side of the main PWB are not coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Blank filler plate (model: P-101)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Coating
: Zn-Cr (black), alumetized steel
Capacity
: 2 positions
Connection
Output
: M3.5 screw terminals (torque 0.8 N·m)
Pneumatic
: Rc 3/8" female (torque ≤12 N·m)
Power input
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Manifold
: Aluminium alloy
Isolation
: I/O to power to FG
INSTALLATION
Power input
•
AC
: 85 – 132 V, 47 – 63 Hz, 15 VA maximum
•
DC
: 24 V DC ±10 %, (ripple 10 % p-p max.)
Operating temperature
: -5 to 55°C (23 to 131°F)
0 to 55°C (32 to 131°F) for AC power
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Angle bracket
Weight
: 2 kg (4.4 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(I/O to power to FG)
Maximum supply pressure
: 196 kPa
(2 kgf/cm
2
, 1.96 bar, 28 psig)
MOUNTING REQUIREMENTS unit: mm (inch)
CONNECTION DIAGRAM