ES-0828 Rev.8
10DU
High-density Signal Conditioners 10-RACK
CURRENT LOOP SUPPLY
(10 – 50 mA loop)
Functions & Features
• Powering a 10 – 50 mA DC current loop
• Isolation
• Shortcircuit protection
• Applicable to smart transmitters
Typical Applications
• Various 2-wire transmitters
MODEL: 10DU–H60-R[1]
ORDERING INFORMATION
• Code number: 10DU-H60-R[1]
Specify a code from below for [1].
(e.g. 10D-H60-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT
Current
H
: 10 – 50 mA DC
OUTPUT 1
Voltage
6
: 1 – 5 V DC (Load resistance 50 kΩ min.)
OUTPUT 2
0
: None
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided
Connection
Input
: M3.5 screw terminals (torque 0.8 N·m)
Output
: Card-edge connector and M3.5 screw terminals (torque 0.8 N·m)
Power input
: Supplied from card-edge connector
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
SUPPLY OUTPUT
Output voltage
: 24 – 28 V DC with no load
Current rating
: ≤ 55mA DC
•
Shortcircuit Protection
Current limited
: Approx. 65 mA
Protected time duration
: No limit
INPUT SPECIFICATIONS
Equivalent input impedance
: Approx. 100 Ω at 50 mA
OUTPUT SPECIFICATIONS
The output goes below 0 % when the input is open.
INSTALLATION
Current consumption
: Approx. 100 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Standard Rack 10BXx
Weight
: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
Supply output
: ±3 % over voltage range
Output signal
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(input to output to power)
1500 V AC @ 1 minute (input or output or power to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM