ES-1821 Rev.15
18VP
Rack-mounted DCS Signal Conditioners 18-RACK
I/P TRANSDUCER
Functions & Features
• Converting a DC input into a proportional standard pneumatic signal
• Semiconductor pressure sensor in the feedback circuit
• High resolution
• No mounting position effect
Typical Applications
• Converting a 4 – 20 mA from a PID controller into a pneumatic signal
MODEL: 18VP–[1][2][3]–R
ORDERING INFORMATION
• Code number: 18VP-[1][2][3]-R
Specify a code from below for each of [1] through [3].
(e.g. 18VP-261-R)
[1] PNEUMATIC CONNECTION
2
: Rc 1/4"
7
: 1/4" NPT fitting
[2] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[3] OUTPUT
1S
: 19.6 – 98.1 kPa
2S
: 20 – 100 kPa
3S
: 20.7 – 103.4 kPa
1
: 0.2 – 1.0 kgf/cm
2
2
: 0.2 – 1.0 bar
3
: 3 – 15 psig
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• Standard rack with air manifold
Note: The 18VP must be installed in a 18-RACK or 18K-RACK series rack with air manifold.
GENERAL SPECIFICATIONS
Construction
: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
Input
: M3.5 screw terminals (torque 0.8 N·m) and connector
Pneumatic
: Rc 1/4" or 1/4" NPT female
(torque ≤ 12 N·m)
Power input
: supplied from connector
Supply pressure
: supplied collectively from the rack
Screw terminal
: Nickel-plated steel
Isolation
: Input to power
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
OUTPUT SPECIFICATIONS
■
Output
:
19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm
2
20 – 100 kPa, 0.2 – 1.0 bar
20.7 – 103.4 kPa, 3 – 15 psig
The output goes below 0 % if the input loop is open.
Maximum air delivery
: 60 Nl/minute (2.1 SCFM)
Maximum air exhaust
: 60 Nl/minute (2.1 SCFM)
INSTALLATION
Supply pressure
: 140 kPa (1.4 kgf/cm
2
, 1.4 bar, 20 psig)
±10 %. Use dry air containing no carbon black or other foreign particles. To ensure reliability use an air filter (0.01 microns).
Air consumption
: 6 Nl/minute (0.21 SCFM)
Current consumption
: Approx. 30 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Standard Rack 18BXx or 18KBXx
Weight
: 250 g (0.55 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.3 % including linearity and repeatability
Linearity
: ±0.2 %
Repeatability
: 0.1 %
Temp. coefficient
: ±0.05 %/°C (±0.03 %/°F)
Response time
: ≤ 3 sec. (0 – 90 %)
Mounting position effect
: ±0.1 % (all dimensions)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(input to power)
1500 V AC @ 1 minute
(input or power to ground)
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM