ES-1846 Rev.5

18YVT

Rack-mounted DCS Signal Conditioners 18-RACK

VOLTAGE GENERATOR

(for testing)
Functions & Features
• Generating DC voltage signals
• Output voltages are easily adjustable
Typical Applications
• Generated voltages can be used for function checks of the entire control system

MODEL: 18YVT–066–R

ORDERING INFORMATION

• Code number: 18YVT-066-R

INPUT

0: None

OUTPUT 1

Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

OUTPUT 2

Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
  Output 1 & 2
: Connector
  Monitor output: M3.5 screw terminals (torque 0.8 N·m)
  Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Output to power
(all outputs internally connected)

OUTPUT SPECIFICATIONS

Output: 1 – 5 V DC
Output adjustment: 270°-turn screwdriver (front)

INSTALLATION

Current consumption: Approx. 15 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span

Line voltage effect: ±0.5 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (output to power)
1500 V AC @ 1 minute (output or power to ground)

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

TERMINAL ASSIGNMENTS

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM