ES-9426 Rev.5
43AL1-B
Digital Panel Meters 43 Series
LOOP POWERED DIGITAL METER
(explosion-proof; outdoor enclosure; process meter)
Functions & Features
• Loop powered -1999 to 9999 compact digital meter
• No external power source needed
• Optional stainless steel enclosure
MODEL:43AL1–B–[1][2][3][4][5]
ORDERING INFORMATION
• Code number: 43AL1–B-[1][2][3][4][5]
Specify a code from below for each of [1] through [5].
(e.g. 43AL1-B-0001/S/Q)
• Specify the specification for option code /Q
(e.g. /SET)
[1] SAFETY APPROVAL
0
: None
3
: FM explosion-proof
8
: TIIS flameproof (CE not available)
Confirm selectable combinations of approval and wiring conduit types in the table.
[2] TERMINAL BLOCK
0
: None (Connection to the rear of digital meter module)
(TIIS approval not selectable)
T
: Incorporated
[3] WIRING CONDUIT
0
: G 1/2
1
: 1/2 NPT
2
: M20 × 1.5
3
: PG 13.5
Confirm selectable combinations of approval and wiring conduit types in the table.
[4] MOUNTING BRACKET
0
: Without
1
: With
[5] OPTIONS (multiple selections)
Enclosure Materials
Blank
: Diecast aluminium enclosure
/S
: Stainless steel enclosure
(TIIS flameproof approval not selectable)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9426)
RELATED PRODUCTS
• Cable gland (model: BX-E-EXP)
• Stopping plug (model: BX-E-SBP)
PACKAGE INCLUDES...
•
Cable gland
: Two provided for TIIS flameproof type
Model No.
: BX-E-EXP
Cable entries
: Elastomeric sealing rings
Wiring conduit size
: G 1/2
Material
: Chrome-plated brass (entry)
CR (sealing ring)
Applicable wire size
: 8 - 12 dia.
•
Stopping plug
: One provided for TIIS flameproof type
Model No.
: BX-E-SBP
Wiring conduit size
: G 1/2
Material
: Diecast aluminium (plug)
NBR (O-ring)
• Mounting screws
Bolt (M8 x 15): 4 pcs.
Spring washer for M8: 4 pcs.
Material: Stainless steel 304
•
Mounting bracket assembly (option)
Mounting bracket: 1 pcs.
M10 U-bolt: 2 pcs.
Nut for M10: 4 pcs.
Spring washer for M10: 4 pcs.
Material:
Stainless steel 304
Applicable pipe
: 1 1/2” min.; 2” max.
•
Engineering unit label (1)
GENERAL SPECIFICATIONS
Degree of protection
: NEMA 4X, IP66/IP67
Wiring conduit:
See ‘Ordering information.’
Connection
:
•
Without terminal block
: Screwless spring terminal in Digital meter
Applicable wire size
: 1.0 to 1.3 mm
2
, stripped length 8 mm
•
With Terminal block
: Euro terminal
Applicable wire size
: 0.2 to 4 mm
2
, stripped length 8 mm
Materials
Meter housing
: Flame-resistant resin (gray)
Enclosure
: Diecast aluminium standard; stainless steel casting optional (equivalent to type 316); silver color, epoxy resin coated
Isolation
: Input to FE (Functional Earth) to outdoor enclosure
A/D conversion
: Σ – Δ
Sampling rate
: 10 times/sec. (100 msec.)
Averaging
: None or moving average
Setting
: (Front button)
• Scaled range
• Moving average
DISPLAY
Display
: 4 digits of 10.2 mm (.4”) height, 7-segment, red LED
Display range
: -1999 to 9999
Scaling range for measurement range
: -1999 to 9999 counts
Decimal point position
: 10
-1
, 10
-2
, 10
-3
or none
Zero indication
: Higher-digit zeros are suppressed.
Over-range indication
: '-1999' or '9999' blinking for display values out of the display range. 'S.ERR' blinks surpassing the permissible range.
Engineering unit indication
: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s
2
, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m
3
, m
3
/sec,
m
3
/min, m
3
/h, Nm
3
/h, N·m, N/m
2
, g, kg, kg/h,
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.
INPUT SPECIFICATIONS
■
DC Current
Current range
: 3.75 to 22 mA DC
Voltage drop
: Approx. 3.5 V with 4 mA; approx. 3.7 V with 20 mA (Equivalent input impedance: Approx. 185 Ω)
(Use of the unit causes voltage drop. For 2-wire transmitter, be sure that the voltage by which 2-wire transmitter can operate is ensured including the voltage drop by other devices and wiring resistance.)
INSTALLATION
Operating temperature
No safety approval
: -40 to +70°C (-40 to +158°F)
FM approval
:
-40 to +70°C (T5)
-40 to +60°C (T6)
TIIS approval
: -20 to +60°C (T6)
Weight
:
• Unit
Approx. 1.5 kg (3.3 lb), aluminium
Approx. 4.0 kg (8.8 lb), stainless steel
Approx. 2.0 kg (4.4 lb), TIIS flameproof
• Mounting bracket assembly (option)
Approx. 0.78 kg (1.72 lb)
PERFORMANCE
Accuracy
:
±0.1 % rdg ±1 digit× scaling-multiple
(When the scaling-multiple is less than 1, rounded up to 1.)
Temp. coefficient
: ±0.3 digits× scaling-multiple/℃
(When the scaling-multiple is less than 1, rounded up to 1.)
Scaling-multiple = | (Display Scaling Value B - Display Scaling Value A) ÷ (default Display Scaling Value B - default Display Scaling Value A) |
Dielectric strength
: 1500 V AC @ 1 minute (input to
enclosure; when FE (Functional Earth) is not connected to
the enclosure.)
500 V DC @ 1 minute
(input to FE (Functional Earth))
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Safety approval
:
FM: Explosion-proof and Dust-ignition proof
Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
T5 and T6
(Class 3615)
TIIS: Flameproof
Ex d IIC T6
EXTERNAL DIMENSIONS unit: mm [inch]
CONNECTION DIAGRAM