ES-9504 Rev.13
47LM
Digital Panel Meters 47 Series
POTENTIOMETER INPUT DIGITAL PANEL METER
(4 digit, LED display type)
Functions & Features
• 4-digit potentiometer input digital panel meter
• 1/8 DIN size
• Moving average function to suppress the display flickering
• Scaling, forced zero, low-end cutout
• Max. and Min. value display
• Rear terminal cover for safety strapped to the meter
• IP66 front panel
• Separable terminal block
MODEL: 47LM-1[1][2][3]-[4][5]
ORDERING INFORMATION
• Code number: 47LM-1[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. 47LM-101G-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
INPUT
Total resistance 100 Ω – 10 kΩ
[1] DC OUTPUT
0
: Without
Current
A
: 4 – 20 mA DC (Load resistance 550 Ω max.)
D
: 0 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 10 kΩ min.)
[2] ALARM OUTPUT
0
: None
1
: N.O. relay contact, 4 points
2
: SPDT relay contact, 2 points
[3] DISPLAY COLOR
R
: Red
YR
: Orange
G
: Green
BG
: Bluegreen
B
: Blue
W
: White
[4] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[5] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
Moving parts and indicators are not coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9504)
GENERAL SPECIFICATIONS
Construction
: Panel flush mounting
Degree of protection
: IP66; applicable to the front of the panel meter mounted according to the specified panel cutout
Connection:
M3 separable screw terminal (torque 0.6 N·m)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to DC output to HH output or H output to
L output or LL output to power
Setting
: (Front button)
• Scaled range
• Alarm setpoint
• Hysteresis (deadband)
• Others
(Refer to the instruction manual for details)
Read rate
: 40 times/sec. (25 msec.)
Averaging
: None or moving average
Lockout setting
: Prohibiting certain operations; protecting settings
DISPLAY
Display
: 16 mm (.63) high, 4 digits, 7-segment LED
Display range
: -9999 to 9999
Decimal point position
: 10
-1
, 10
-2
, 10
-3
or none
Zero indication
: Higher-digit zeros are suppressed.
Over-range indication
: ‘-9999’ or ‘9999’ blinking for display values out of the display range.
Alarm status indication
LL indicator
: Green LED turns on when the LL alarm is tripped.
L indicator
: Green LED turns on when the L alarm is tripped.
H indicator
: Red LED turns on when the H alarm is tripped.
HH indicator
: Red LED turns on when the HH alarm is tripped.
P indicator
: Amber LED turns on when none of the other alarms is tripped.
Only ‘P’ turns on with no-alarm-output type. ‘LL’ or ‘HH’ does not turn on with dual-alarm-output type.
All setpoints can be independently set either for Hi or Lo alarm trip.
Function indicators
:
Zro, Spn, D/P, Tch, Fnc, Min, Max
Display mode status and operation status, amber ON or blink
Engineering unit indication
: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s
2
, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m
3
, m
3
/sec,
m
3
/min, m
3
/h, Nm
3
/h, N·m, N/m
2
, g, kg, kg/h,
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, min
-1
, pH, %, ppm, etc.
INPUT SPECIFICATIONS
Minimum span
: 10 % of total resistance
Excitation
: 1.2 V DC
OUTPUT SPECIFICATIONS
■
DC Output
•
DC Current
Operational range
: -5 – +105 %
•
DC Voltage
Operational range
: -5 – +105 %
■
Alarm Output
: Relay contact
Rated load
: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage
: 250 V AC, 30 V DC
Maximum switching power
: 750 VA, 90 W (resistive load)
Minimum load
: 5 V DC @ 10 mA
Mechanical life
: ≥ 5 × 10
6
cycles (rate 180 cycles/min.)
INSTALLATION
Power consumption
•
AC
: Approx. 6.5VA
•
DC
: Approx. 3 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Panel flush mounting
Weight
: 300 g (0.66 lb)
PERFORMANCE in percentage of max. span
Accuracy
Display
: ±0.1 % ±1 digit
Output
: ±0.1 % (DC output = display + output)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Input resolution
: Max. 16 bits
Output resolution
: Max. 14 bits
Response time
: ≤ 0.5 sec.
(alarm output: 0 – 100 % at 90 % setpoint)
≤ 0.5 sec. (DC output: 0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (input to DC output to HH output or H output to L output or LL output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (alarm output)
Installation Category II (power)
Pollution degree 2
Input or DC output to alarm output to power: Reinforced insulation (300 V)
Input to DC output: Basic insulation (300 V)
RoHS Directive
Protection against access to the terminal blocks
:
Finger protection (VDE 0660-514)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM