ES-6487 Rev.11
54U
Power Transducer Series
MULTI POWER MONITOR
(4 digital displays)
Functions & Features
• Measures simultaneously several variables of a heavy-current power system: current, voltage, active, reactive and apparent power, active and reactive energy, power factor, frequency, etc.
• All measured values, counter values, display mode, setting data are stored in the non-volatile memory at the power off
• Parameters are programmable using the front buttons or the PC via infrared interface
• Mounted using M5 screws or mounting brackets
• 60-segment bargraph
• Displayed measurands are freely selectable
• Open collector output for alarm or energy count
• Loop test output
Typical Applications
• Multi-functional power monitor incorporated in an electric device: saves space, wiring works, and cost
MODEL: 54U-[1][2][3][4]-AD4[5]
ORDERING INFORMATION
• Code number: 54U-[1][2][3][4]-AD4[5]
Specify a code from below for each of [1] through [5].
(e.g. 54U-1211-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
[1] CONFIGURATION
1
: Single phase / 2-wire and 3-wire, 3-phase / 3-wire
2
: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[2] INPUT
1
: 480 V / 1 A AC
2
: 480 V / 5 A AC
[3] DISCRETE INPUT
0
: None
('External Interface' codes 1, 2, 3, 7 and 8 Not selectable.)
1
: 24V DC
('External Interface' codes 4, 5, 6, 9 and A Not selectable.)
2
: 110V DC
('External Interface' codes 4, 5, 6, 9 and A Not selectable.)
[4] EXTERNAL INTERFACE
1
: Modbus, Do × 1, Di × 1
2
: 4 – 20 mA DC × 4, Do × 1, Di × 1
3
: 1 – 5 V DC × 4, Do × 1, Di × 1
4
: Modbus, Do × 2
5
: 4 – 20 mA DC × 4, Do × 2
6
: 1 – 5 V DC × 4, Do × 2
7
: 4 – 20 mA DC × 4 (isolated), Do × 1, Di × 1
8
: 1 – 5 V DC × 4 (isolated), Do × 1, Di × 1
9
: 4 – 20 mA DC × 4 (isolated), Do × 2
A
: 1 – 5 V DC × 4 (isolated), Do × 2
AUXILIARY POWER SUPPLY
AD4
: universal
100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
[5] OPTIONS (multiple selections)
Language
blank
: Japanese
/E
: English
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
Moving parts and indicators are not coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-6487)
RELATED PRODUCTS
• Infrared Communication Adaptor (model: COP-IRU)
• PC configurator software (model: PMCFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Construction
: 110-mm square panel flush mounted
Degree of protection
Front panel
: IP 50
Terminal block, housing
: IP 30
Connection
Voltage input
: M4 screw terminals (torque 1.4 N·m)
Current input
: M4 screw terminals (torque 1.4 N·m)
Discrete input, discrete output, analog output, Modbus, auxiliary power supply
: M3 screw terminals (torque 0.6 N·m)
Configuration
Code 1
: Single phase/2-wire and 3-wire, 3-phase/3- wire balanced/unbalanced load
Code 2
: Single phase/2-wire and 3-wire, 3-phase/3- wire balanced/unbalanced load, 3-phase/4- wire balanced/unbalanced load
Screw terminal
• M3 screw
: Nickel-plated steel (standard) or stainless steel
• M4 screw
: Nickel-plated brass (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Voltage input to current input to discrete input to Modbus or analog output to discrete output to power
Note: Isolated between each analog output for ‘External interface’ codes 7, 8, 9 and A
■
Measured variables
Voltage
: 1 – 2, 2 – 3, 3 – 1, 1 – N, 2 – N, 3 – N
Current
: 1, 2, 3, N
Active / reactive / apparent power
: 1, 2, 3, Σ
Power factor
: 1, 2, 3, Σ
Frequency
Phase angle between voltages
: 1 – 2, 2 – 3, 3 – 1
Active energy incoming / outgoing
: Σ
Reactive energy inductive / capacitive
: Σ
Apparent energy
: Σ
Active / reactive / apparent power intervals (demand)
Current intervals (demand)
: 1, 2, 3, N
Harmonic contents
: Σ, 2nd to 31st
Voltage
: 1 – 2, 2 – 3, 3 – 1, 1 – N, 2 – N, 3 – N
Current
: 1, 2, 3, N
Max. and min. values
:
1 = R, 2 = S, 3 = T
Infrared communication
: Transmission distance max. 1 meter (for use with the COP-IRU and PMCFG)
■
DISPLAY
: LCD with LED backlight (LED OFF timer available)
Signed
: 4 digits, 2 lines
Energy
: 9 digits, 1 line
Bargraph
: 1 point (60 segments)
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 65 Hz)
•
Voltage Input
Rated voltage
Line-to-line (delta voltage)
: 480 V
Line-neutral (phase voltage)
: 277 V
Consumption VA
: ≤ U
LN
2
/ 300 kΩ / phase
Overload capacity
: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
Rated current
: 1 A or 5 A
Consumption VA
: ≤ I
2
· 0.01 Ω / phase
Overload capacity
: 4000 % of rating for 1 sec., 2000 % for
4 sec., 120 % continuous
Selectable primary current range
: 1 – 20 000 A
Operational range
Voltage, current, apparent power
: ≤ 120 % of the rating
Active / reactive power
: -120 to +120 % of the rating
Frequency
: 45 – 65 Hz
Power factor
: -1 to +1
■
Discrete Input
: 24 V DC or 110 V DC
(input resistance 6 kΩ)
Detecting voltage
: External 24 V DC ±10 % or 110 V DC ±10 %
ON current
: ≥ 1 mA (≤ 24 kΩ @ 24 V, ≤ 110 kΩ @110 V)
OFF current
: ≤ 0.1 mA (≥ 240 kΩ @ 24 V, ≥ 1.1 MΩ @ 110 V)
Detecting time
: 10 – 1000 msec.
The status can be monitored on the Modbus; usable to reset energy count or to update average (demand) value.
OUTPUT SPECIFICATIONS
■
Modbus
Communication
: Half-duplex, asynchronous, no procedure
Interface
: Conforms to TIA/EIA-485-A
Max. transmission distance
: 500 meters
Baud rate
: 1.2 – 38.4 kbps
Max. number of nodes
: 31 (except the master)
Protocol
: Modbus RTU
Node address
: 1 – 247 (factory default setting: 1)
Parity
: none, even or odd (factory default setting: odd)
Stop bit
: 1 or 2 (factory default setting: 1)
Media
: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
■ DC Current
: 4 – 20 mA DC
Load resistance
: ≤ 270 Ω
Measurands converted into analog output
: Voltage, Current, Active / reactive / apparent power, Power factor, Frequency, Harmonic contents
■
DC Voltage
: 1 – 5 V DC
Load resistance
: ≥ 5000 Ω
Measurands converted into analog output
: Voltage, Current, Active / reactive / apparent power, Power factor, Frequency, Harmonic contents
■
Open Collector
Programmable for either alarm or energy count.
Max. rated load
: 130 V DC @50 mA
Continuous rated load
: 130 V DC @30 mA
Saturation voltage
: 1.5 V DC
Measurands applicable to alarm
: Voltage, current, current intervals, neutral current, frequency, energy, energy intervals
(ON delay, deadband and other parameters are selectable)
Measurands applicable to count
: Energy;
Pulse rate selectable within
0.1 – 10 000.0 kWh/p, kvarh/p, kVAh/p
INSTALLATION
Power consumption
•
AC
: < 8 VA; Less than 13 VA for 'External interface' code 7 and 9
•
DC
: < 4 W; Less than 6 W for 'External interface' code 7 and 9
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +80°C (-4 to +176°F)
Operating humidity
: 0 to 90 %RH (non-condensing)
Mounting
: Panel flush mounting (M5 screws (torque 2 N·m) or mounting brackets)
Weight
Configuration Code 1
: 500 g (1.1 lb)
Configuration Code 2
: 525 g (1.16 lb)
PERFORMANCE
Accuracy
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)
Voltage
:
(accur.±0.3 %)
Rated voltage at ≥ 100 V
100 V at < 100 V
Current
: (accur.±0.3 %)of Span 1 A or 5 A
Power
: (accur.±0.5 %)
Rated voltage/current at ≥ 100 V
Wattage as listed below at < 100 V:
173.2 W (1 A) or 866 W (5 A) for 3 ph/3 w
100 W (1 A) or 500 W (5 A) for 1 ph/2 w
200 W (1 A) or 1000 W (5 A) for 1 ph/3 w
300 W (1 A) or 1500 W (5 A) for 3 ph/4 w
PF
: (accur.±0.5 %)
Frequency
:
(accur.±0.1 %) of span
Energy
:
(accur.±1 %)
Harmonic
:
(accur.±1 %) of span
Analog output
: Accuracy of assigned measurand or ±0.2 %, whichever is greater.
Sampling rate
: 64 samples per cycle
Data update period
:
Harmonic contents and frequency
: ≤ 1.1 sec.
Other
: ≤ 600 msec.
Response time
: ≤ 2 sec. (0 – 99 %),
≤ 3 sec. for frequency and harmonic contents
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(voltage input to current input to discrete input to Modbus or analog output to discrete output to power)
500 V AC @1 minute for 'External interface' code 7, 8, 9 and A (between each analog output)
2000 V AC @1 minute (circuits to housing)
MOUNTING REQUIREMENTS
EXTERNAL VIEW
TERMINAL CONNECTIONS
MODBUS WIRING CONNECTION
EXTERNAL DIMENSIONS unit: mm [inch]
SYSTEM CONFIGURATION EXAMPLES