ES-6602 Rev.11

60C

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(CC-Link)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with CC-Link
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60C-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 60C-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 60C-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] NO. OF CHANNELS

04: 4 points
08: 8 points
16: 16 points

[2] I/O TYPE

1: Input
2: Output

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)

PACKAGE INCLUDES...

• Terminating resistor (110 Ω, 0.5 W)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  CC-Link
: Euro type connector terminal (applicable wire
  size: 0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: 34-pin connector (OMRON XG4A-3434)
  Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to CC-Link to power to FG1
Power indicator: Green LED turns on with power supplied.

CC-Link COMMUNICATION

CC-Link: Conforms to Version 1.10
Station type: Remote device station
Station No. setting: Rotary switch; 1 – 64
Number of occupied stations:
    60C-04 1 station
    60C-08 2 stations
    60C-16 4 stations
    Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting: Rotary switch
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps, 10Mbps)
Transmission cable: Approved for CC-Link
L RUN indicator: Red LED turns on in an normal condition.
L ERR. indicator: Red LED turns on or flashes in an abnormality; off with wire breakdown.
SD indicator: Red LED turns on when transmitting.
RD indicator: Red LED turns on when receiving.

INPUT SPECIFICATIONS

Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

OUTPUT SPECIFICATIONS

Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

INSTALLATION

Power consumption
AC: Approx. 4 VA
DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to CC-Link to power)
2000 V AC @ 1 minute (input or output or CC-Link or power to FG1)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

■ COMMUNICATION CABLE CONNECTIONS