ES-6604 Rev.16

60D

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(DeviceNet)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with DeviceNet
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60D-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 60D-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 60D-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] NO. OF CHANNELS

04: 4 points
08: 8 points
16: 16 points

[2] I/O TYPE

1: Input
2: Output

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
(CE not available)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)
• Programming Unit (model: PU-2x)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  DeviceNet
: Euro type connector terminal (applicable
  wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: 34-pin connector (OMRON XG4A-3434)
  Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to DeviceNet to power to FG1
Power indicator: Green LED turns on with power supplied.

DeviceNet COMMUNICATION

Transmission cable: Approved for DeviceNet
Node address setting: DIP switch; 00 – 63
Baud rate setting: DIP switch
MS (Module Status) indicator: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.

INPUT SPECIFICATIONS

Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
 (-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog input range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog input range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

OUTPUT SPECIFICATIONS

Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
(-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog output range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog output range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

INSTALLATION

Power consumption
AC: Approx. 4 VA
DC: Approx. 4 W (160 mA)
Supply voltage to network: 11 – 25 V DC supplied through the network terminal block
Supply current to network: 60 mA max. @  24 V
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to DeviceNet to power)
2000 V AC @ 1 minute (input or output or DeviceNet or power to FG1)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG1 terminal to ground.
Caution: FG1 terminal is NOT a protective conductor terminal.