ES-6610 Rev.4
60F
Field Network Modules 60-UNIT Series
ANALOG I/O MODULE
(Fuji Electric T-Link use)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with T-Link
• Saving power and I/O wiring inside an instrumentation panel
MODEL: 60F-16[1]-[2][3]
ORDERING INFORMATION
• Code number: 60F-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 60F-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
NO. OF CHANNELS
16
: 16 points
[1] I/O TYPE
1
: Input
2
: Output
[2] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
•Special cable (model: MCN34)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
T-Link
: Euro type connector terminal (applicable wire size:
0.2 to 2.5 mm
2
, stripped length 7 mm)
I/O
: 34-pin connector (OMRON XG4A-3434)
Power input
: M3.5 screw terminal
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: I/O to T-Link to power to FG1
Power indicator
: Green LED turns on with power supplied.
T-Link SPECIFICATIONS
Configuration
: Multi-drop
Communication
: Half-duplex
Baud rate
: 500 kbps
Transmission media/distance
:
KPEV-SB 0.75 mm
2
× 1 pair, 700 m
T-KPEV-SB, 1.25 mm
2
× 1 pair, 1000 m
Station No.
: Rotary switch; 00 - 99
(Factory default setting: 00)
L RUN indicator
: Red LED ON at normal communication
L ERR. indicator
: Red LED ON/blinking at communication abnormality
L I/O indicator
: Red LED blinking at normal I/O
L COM indicator
: RED LED blinking at T-Link normal communication
■
NUMBER OF CONNECTABLE UNITS WITH T-Link
Up to a maximum of 32 T-Link devices can be connected in a single T-Link system. There is a limit of 100 words in processor memory. Make sure that the configured word area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to this device.
The below describes the number of words occupied per device by number of modules.
•
For input 16 / output 16 modules
: 16
INPUT SPECIFICATIONS
■
Analog Input
Input range
: 1 – 5 V DC
Input resistance
: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output
: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
OUTPUT SPECIFICATIONS
■
Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range
: 1 – 5 V DC
Load resistance
: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output
: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
INSTALLATION
Power consumption
•
AC
: Approx. 3 VA
•
DC
: Approx. 4 W (160 mA)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail
Weight
: 450 g (0.99 lb)
PERFORMANCE in percentage of span
A/D conversion
: ±0.1 %
D/A conversion
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration
: ≤ 10 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or output to T-Link to power)
2000 V AC @ 1 minute (input or output or T-Link or power to FG1)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM