ES-6610 Rev.4

60F

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(Fuji Electric T-Link use)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with T-Link
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60F-16[1]-[2][3]

ORDERING INFORMATION

• Code number: 60F-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
  (e.g. 60F-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

NO. OF CHANNELS

16: 16 points

[1] I/O TYPE

1: Input
2: Output

[2] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  T-Link
: Euro type connector terminal (applicable wire size:
  0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: 34-pin connector (OMRON XG4A-3434)
  Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to T-Link to power to FG1
Power indicator: Green LED turns on with power supplied.

T-Link SPECIFICATIONS

Configuration: Multi-drop
Communication: Half-duplex
Baud rate: 500 kbps
Transmission media/distance:
  KPEV-SB 0.75 mm2 × 1 pair, 700 m
  T-KPEV-SB, 1.25 mm2 × 1 pair, 1000 m
Station No.: Rotary switch; 00 - 99
(Factory default setting: 00)
L RUN indicator: Red LED ON at normal communication
L ERR. indicator: Red LED ON/blinking at communication abnormality
L I/O indicator: Red LED blinking at normal I/O
L COM indicator: RED LED blinking at T-Link normal communication
NUMBER OF CONNECTABLE UNITS WITH T-Link
Up to a maximum of 32 T-Link devices can be connected in a single T-Link system. There is a limit of 100 words in processor memory. Make sure that the configured word area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to this device.
The below describes the number of words occupied per device by number of modules.
For input 16 / output 16 modules: 16

INPUT SPECIFICATIONS

Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

OUTPUT SPECIFICATIONS

Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

INSTALLATION

Power consumption
AC: Approx. 3 VA
DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to T-Link to power)
2000 V AC @ 1 minute (input or output or T-Link or power to FG1)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM