ES-6606 Rev.13
60M
Field Network Modules 60-UNIT Series
ANALOG I/O MODULE
(Modbus; RS-485)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with Modbus
• Saving power and I/O wiring inside an instrumentation panel
MODEL: 60M-16[1]-[2][3]
ORDERING INFORMATION
• Code number: 60M-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 60M-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
NO. OF CHANNELS
16
: 16 points
[1] I/O TYPE
1
: Input
2
: Output
[2] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
•Special cable (model: MCN34)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.25 W)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
Modbus
: Euro type connector terminal (applicable wire
size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
I/O
: 34-pin connector (OMRON XG4A-3434)
Power input
: M3.5 screw terminal
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: I/O to Modbus to power to FG1
Power indicator
: Green LED turns on with power supplied.
MODBUS COMMUNICATION
Communication
: Conforms to TIA/EIA-485-A
Transmission setting
: DIP switch
Data
: RTU (Binary) or ASCII
Parity
: none, even or odd
Baud rate
: 4800, 9600, 19.2 k, 38.4 k (bps)
Node address setting
: Rotary switch; 01 – F7
(factory setting: 00)
L RUN indicator
: Red LED turns on for 10 sec. when the module receives data.
L ERR. indicator
: Red LED turns on at errors in parity, framing, overrun, CRC or LRC.
SD indicator
: Red LED turns on when transmitting.
RD indicator
: Red LED turns on when receiving.
Analog input
: Programming Unit (model: PU-2x) or via Modbus
Moving averaging
: None, every 2 or 4 samples
Sampling rate
: 400, 240, or 160 (msec.)
INPUT SPECIFICATIONS
■
Analog Input
Input range
: 1 – 5 V DC
Input resistance
: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
■
A/D Conversion Output
•
Signed binary
(2-byte data)
Signal range 0 – 100 % is proportional to hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
•
Floating data
(4-byte data)
Initial signal range 0 – 100 % is proportional to 0 – 10000, that is possible to be scaled into a specific range.
OUTPUT SPECIFICATIONS
■
Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range
: 1 – 5 V DC
Load resistance
: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
■
D/A Conversion Input
•
Signed binary
(2-byte data)
Signal range 0 – 100 % is proportional to hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
•
Floating data
(4-byte data)
Initial signal range 0 – 100 % is proportional to 0 – 10000, that is possible to be scaled into a specific range.
INSTALLATION
Power consumption
•
AC
: Approx. 4 VA
•
DC
: Approx. 4 W (160 mA)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail
Weight
: 450 g (0.99 lb)
PERFORMANCE in percentage of span
A/D conversion
: ±0.1 %
D/A conversion
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration
: ≤ 10 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or output to Modbus to power)
2000 V AC @ 1 minute (input or output or Modbus or power to FG1)
EXTERNAL VIEW
MODBUS FUNCTION CODES & SUPPORTED CODES
MODBUS I/O ASSIGNMENT
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ COMMUNICATION CABLE CONNECTIONS