ES-6627 Rev.9
61C
Field Network Modules 61-UNIT Series
ANALOG I/O MODULE
(CC-Link)
Functions & Features
• Interfacing analog I/O signals from/to Mini-M, Pico-M and other signal conditioner modules with CC-Link
• Saving power and I/O wiring inside an instrumentation panel
MODEL: 61C-[1][2]-[3][4]
ORDERING INFORMATION
• Code number: 61C-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. 61C-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] NO. OF CHANNELS
04
: 4 points
08
: 8 points
16
: 16 points
[2] I/O TYPE
1
: Input
2
: Output
3:
Input/output (Select 16 for no. of channels)
(8 points for input, 8 points for output)
(Use Installation Base model: M8BS2-164)
[3] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the 61C is to be
combined with the M8BS2.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
CC-Link
: Euro type connector terminal (applicable wire
size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
I/O
: Via Installation Base (model: MxBS2)
Power input
: Via Installation Base (model: MxBS2)
Housing material
: Flame-resistant resin (black)
Isolation
: I/O to CC-Link to power
Power indicator
: Green LED turns on with power supplied.
CC-Link COMMUNICATION
CC-Link
: Conforms to Version 1.10
Station type
: Remote device station
Station No. setting
: Rotary switch; 1 – 64
Number of occupied stations:
61C-04x: 1 station
61C-08x: 2 stations
61C-161: 4 stations
61C-162: 4 stations
61C-163: 2 stations
Remote I/O (RX, RY) is fixed to 32 points.
Baud rate setting
: Rotary switch
(156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps, 10Mbps)
Transmission cable
: Approved for CC-Link
L RUN indicator
: Red LED turns on in an normal condition.
L ERR. indicator
: Red LED turns on or flashes in an abnormality; off with wire breakdown.
SD indicator
: Red LED turns on when transmitting.
RD indicator
: Red LED turns on when receiving.
INPUT SPECIFICATIONS
■
Analog Input
Input range
: 1 – 5 V DC
Input resistance
: ≥ 1 MΩ
(Each input must be isolated by signal conditioners. Non-isolated modules such as M2BW and M8BW are not usable.)
A/D conversion
Moving averaging
: 4 samples
Sampling rate
: 160 ms
A/D conversion output
: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
OUTPUT SPECIFICATIONS
■
Analog Output
Output range
: 1 – 5 V DC
Load resistance
: 20 kΩ minimum
(Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW
and M8BW are not usable. )
D/A conversion input
: Signed binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 2710 (0 – 10000).
-15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.
INSTALLATION
Power consumption
•
AC
: Approx. 4 VA
•
DC
: Approx. 4 W (160 mA)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: MxBS2)
Weight
: 250 g (0.55 lb)
PERFORMANCE in percentage of span
A/D conversion
: ±0.1 %
D/A conversion
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration
: ≤ 10 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(I/O to CC-Link to power)
EXTERNAL VIEW
A:
Modular jack for factory calibration
B:
Power LED
C:
Station No. Setting
D:
Baud rate Setting
E:
Status indicator LED
F:
Euro type connector terminal for CC-Link
COMMUNICATION CABLE CONNECTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM