MODEL: 61D-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 61D-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 61D-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] NO. OF CHANNELS

04: 4 points
08: 8 points
16: 16 points

[2] I/O TYPE

1: Input
2: Output

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
(CE not available)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the UNIT is to be
combined with the M8BS2.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
• Programming Unit (model: PU-2x)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
 DeviceNet
: Euro type connector terminal (applicable
  wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
 I/O: Via the Installation Base (model: MxBS2)
 Power input: Via the Installation Base (model: MxBS2)
Housing material: Flame-resistant resin (black)
Isolation: I/O to DeviceNet to power
Power indicator: Green LED turns on with power supplied.

DeviceNet COMMUNICATION

Transmission cable: Approved for DeviceNet
Node address setting: DIP switch; 00 – 63
Baud rate setting: DIP switch
MS (Module Status) indicator: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.

INPUT SPECIFICATIONS

Analog Input
Input range: 1 – 5 V DC
Input resistance: ≥ 1 MΩ
(Each input must be isolated by signal conditioners. Non-isolated modules such as M2BW and M8BW are not usable.)
A/D conversion
Moving averaging
: 4 samples
Sampling rate: 160 ms
A/D conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
(-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog input range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog input range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

OUTPUT SPECIFICATIONS

Analog Output
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
(Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW
and M8BW are not usable. )
D/A conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
(-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog output range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog output range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

INSTALLATION

Power consumption
AC: Approx. 4 VA
DC: Approx. 4 W (160 mA)
Supply voltage to network: 11 – 25 V DC supplied through the network terminal block
Supply current to network: 60 mA max. @  24 V
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: MxBS2)
Weight: 250 g (0.55 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(I/O to DeviceNet to power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW