ES-6635 Rev.3

61F

Field Network Modules 61-UNIT Series

ANALOG I/O MODULE

(Fuji Electric T-Link use)
Functions & Features
• Interfacing analog I/O signals from/to Mini-M or Pico-M modules with T-LINK
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 61F-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 61F-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 61F-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] NO. OF CHANNELS

04: 4 points
08: 8 points
16: 16 points

[2] I/O TYPE

1: Input
2: Output

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the UNIT is to be
combined with the M8BS2.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  T-Link
: Euro type connector terminal (applicable wire
  size: 0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: Via Installation Base (model: MxBS2)
  Power input: Via Installation Base (model: MxBS2)
Housing material: Flame-resistant resin (black)
Isolation: I/O or T-Link to power
Power indicator: Green LED turns on with power supplied.

T-Link SPECIFICATIONS

Configuration: Multi-drop
Communication: Half-duplex
Baud rate: 500 kbps
Transmission media/distance:
  KPEV-SB 0.75 mm2 × 1 pair, 700 m
  T-KPEV-SB, 1.25 mm2 × 1 pair, 1000 m
Station No.: Rotary switch; 00 - 99
(Factory default setting: 00)
L RUN indicator: Red LED ON at normal communication
L ERR. indicator: Red LED ON/blinking at communication abnormality
L I/O indicator: Red LED blinking at normal I/O
L COM indicator: RED LED blinking at T-Link normal communication
NUMBER OF CONNECTABLE UNITS WITH T-LINK
Up to a maximum of 32 T-LINK devices can be connected in a single T-LINK system. There is a limit of 100 words in processor memory. Make sure that the configured word area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to this device.
The below describes the number of words occupied per device by number of modules.
For input 4 / output 4 modules: 4
For input 8 / output 8 modules: 8
For input 16 / output 16 modules: 16

INPUT SPECIFICATIONS

Analog Input
Input range: 1 – 5 V DC
Input resistance: ≥ 1 MΩ
(Each input must be isolated by signal conditioners. Non-isolated modules such as M2BW and M8BW are not usable.)
A/D conversion
Moving averaging
: 4 samples
Sampling rate: 160 ms
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000).  -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

OUTPUT SPECIFICATIONS

Analog Output
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
(Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW and M8BW are not usable. )
D/A conversion input: Signed binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 2710 (0 – 10000).
-15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

INSTALLATION

Power consumption
AC: Approx. 3 VA
DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: MxBS2)
Weight: 250 g (0.55 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration: ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (I/O or T-Link to power)

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM