ES-1613-A Rev.6
ASL
Plug-in Signal Conditioners M-UNIT
DC ALARM
(rotary switch adjustments)
Functions & Features
• Providing relay contact closures at preset DC input levels
• Dual (Hi/Lo) trip
• Rotary switch setpoint adjustments
• Enclosed relays
• Relays can be powered 110 V DC
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Annunciator
• Various alarm applications
MODEL: ASL–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: ASL-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. ASL-62-B/Q)
• Special input range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
A1
: 4 – 20 mA DC (Input resistance 50 Ω)
B
: 2 – 10 mA DC (Input resistance 500 Ω)
C
: 1 – 5 mA DC (Input resistance 1000 Ω)
D
: 0 – 20 mA DC (Input resistance 50 Ω)
E
: 0 – 16 mA DC (Input resistance 62.5 Ω)
F
: 0 – 10 mA DC (Input resistance 100 Ω)
G
: 0 – 1 mA DC (Input resistance 1000 Ω)
H
: 10 – 50 mA DC (Input resistance 100 Ω)
J
: 0 – 10 μA DC (Input resistance 1000 Ω)
K
: 0 – 100 μA DC (Input resistance 1000 Ω)
GW
: -1 – +1 mA DC (Input resistance 1000 Ω)
FW
: -10 – +10 mA DC (Input resistance 100 Ω)
Z
: Specify current (See INPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Input resistance 10 kΩ min.)
15
: 0 – 50 mV DC (Input resistance 10 kΩ min.)
16
: 0 – 60 mV DC (Input resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Input resistance 100 kΩ min.)
3
: 0 – 1 V DC (Input resistance 1 MΩ min.)
4
: 0 – 10 V DC (Input resistance 1 MΩ min.)
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W
: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W
: -5 – +5 V DC (Input resistance 1 MΩ min.)
0
: Specify voltage (See INPUT SPECIFICATIONS)
[2] OUTPUT
2
: Relay; N.O. or make contact
3
: Relay; N.C. or break contact
[3] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Setpoint adjustments:
10-position rotary switches (front); 0 – 99 % independently; 1 % increments
Hysteresis (deadband)
: 1 – 2.5 %
Front LEDs
: Red LED turns on when the coil is energized.
Power ON timer
: Relays de-energized for approx. 2 seconds after power is turned on.
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
Specify input resistance value for code Z.
■
DC Voltage
: -300 – +300 V DC
Minimum span
: 10 mV
Offset
: Max. 1.5 times span
Input resistance
Span 10 – 100 mV : ≥ 10 kΩ
Span 0.1 – 1 V : ≥ 100 kΩ
Span ≥ 1 V : ≥ 1 MΩ
OUTPUT SPECIFICATIONS
■
Relay Contact:
100 V AC @1 A (cos ø = 1)
120 V AC @1 A (cos ø = 1)
240 V AC @0.5 A (cos ø = 1)
30 V DC @1 A (resistive load)
Maximum switching voltage:
380 V AC or 125 V DC
Maximum switching power:
120 VA or 30 W
Minimum load:
5 V DC @10 mA
Mechanical life:
5 × 10
7
cycles
For maximum relay life with inductive loads, external protection is recommended.
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
•
DC
: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.)
approx. 2 W (80 mA at 24 V)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (0.88 lb)
PERFORMANCE in percentage of span
Setpoint accuracy
: ±0.5 %
Trip point repeatability
: ±0.05 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 0.5±0.2 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM