ES-7516 Rev.10
B3FP
Space-saving Two-wire Signal
Conditioners B3-UNIT
FREQUENCY TRANSMITTER
(field-configurable)
Functions & Features
• Converts the output from a pulse-type transducer
into a 4 – 20 mA DC signal
• DIP switch configurable input range
• Monitor terminals
• High-density mounting
MODEL: B3FP[1]
ORDERING INFORMATION
• Code number: B3FP[1]
Specify a code from below for [1].
(e.g. B3FP/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Orders will be shipped with default factory settings as shown below.
• Factory default setting:
Input type: Voltage pulse
Frequency range: 0 – 1000 Hz
Pulse amplitude: 5 Vp-p
DC offset: 2.5 V
Pulse sensing: DC coupled
Noise filter: None
Detecting level: High (2 V)
INPUT – Field-selectable
Open collector
Voltage pulse
Two-wire current pulse
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating (UL not available)
GENERAL SPECIFICATIONS
Construction
: Small-sized front terminal structure
Connection
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to output
DIP/rotary switches
: For input calibration
(Refer to the instruction manual)
Noise filter
: Chattering protection filter selectable with DIP switches (time constant 1 msec.)
Pulse sensing
: DC coupled or capacitor coupled selectable with DIP SW
INPUT SPECIFICATIONS
Measurable frequencies
: 0 – 0.01 Hz through 100 kHz; Sine waves with frequencies lower than 0.1 Hz cannot be detected with capacitor coupling.
Pulse width time requirement
: Min. 4 μsec. for both H and L levels
DC offset
: Selectable within the maximum voltage for respective pulse amplitude setting.
(e.g. For the amplitude 2 Vp-p with the maximum voltage 10 V, DC offset can be as low as -9 V and as high as +9 V.)
Frequency offset
: Selectable up to 50 % of the full-scale frequency.
■
Open Collector
Sensing voltage/current
: Approx. 2.5 V DC @ 1mA
Detecting levels
: ≤ 750 Ω / 0.7 V for ON;
≥ 3.0 kΩ / 1.3 V for OFF
■
Voltage Pulse
Waveform
: Square or sine
Input impedance
: 10 kΩ min.
Input amplitude
: Min. 0.1 V p-p, max. 200 Vp-p
Max. voltage between input terminals
: 100 V
(Max. voltage across the input terminals: 70 V for conform with EU Directive; 30 V rms, 42.4 V peak or 60 V DC for UL approval)
Detecting level
: See the table below
■
Two-wire Current Pulse
Input resistance
: Receiving resistor 200 Ω
Input range
: 0 – 25 mA
Detecting level
: See the table below
(Convert current into voltage using the receiving resistor value.)
OUTPUT SPECIFICATIONS
Output
: 4 – 20 mA DC
Load resistance vs. supply voltage:
Load Resistance (Ω) = (Supply Voltage (V) – 12 (V)) ÷ 0.02 (A) (including leadwire resistance)
INSTALLATION
Supply voltage
: 12 – 45 V DC
Operating temperature
:
-40 to +85°C (-40 to +185°F)
Max. 55°C (131°F) for UL approval
Operating humidity
: 0 to 95 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 80 g (2.8 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 % (±0.3 % for frequencies below 10 Hz for sine waves detected with capacitor coupling)
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Response time
: Max. 0.5 sec. + 1 pulse cycle (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute
(input to output to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.1010-1)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM