ES-7341 Rev.4
BA8BM-DAC8
Remote Control / Supervisory System BA8 Series
DISCRETE INPUT & RELAY OUTPUT MODULE, 4 points each
(BACnet MS/TP)
MODEL: BA8BM-DAC8-M2
ORDERING INFORMATION
• Code number: BA8BM-DAC8-M2
COMMUNICATION TYPE
BM
: BACnet MS/TP
I/O TYPE
DAC8
: 4-point dry contact inputs, 4-point relay contact outputs
POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
GENERAL SPECIFICATIONS
Connection
BACnet MS/TP
: Tension clamp terminal block
I/O
: Tension clamp terminal block
P
ower input
: Tension clamp terminal block
Housing material
: Flame-resistant resin (gray)
Isolation
: BACnet MS/TP to contact input to contact output to power to FE
Output Mode
: Settable with side DIP switch
Simulated I/O
: Settable with front DIP switch
Output
: Settable with front DIP switch
Status indicator LEDs
: PWR, RUN, ERR, SD, RD (Refer to the instruction manual)
I/O status indicator LEDs
: Green LED with I/O ON
BACnet COMMUNICATION
Applicable standard
:
ANSI/ASHRAE Standard 135-2010
BACnet stansdard device profile:
BACnet Application Specific Controller (B-ASC)
Number of supported object
: 9 max.
Supported object type
:
Binary Input, Binary Output, Device, Accumulator
Supported BIBBs
:
・Data Sharing
Read Property-B (DS-RP-B)
Read Property Multiple-B (DS-RPM-B)
Write Property-B (DS-WP-B)
Write Property Multiple-B (DS-WPM-B)
COV-B (DS-COV-B)
・Device Management
Dynamic Device Binding-B (DM-DDB-B)
Dynamic Object Binding-B (DM-DOB-B)
Device Comunication Control-B (DM-DCC-B)
Time Synchronization-B (DM-TS-B)
UTC Time Synchronization-B (DM-UTC-B)
Supported data link layer
:
MS/TP master (Clause9)
Supported character code
:
ISO 10646 (UTF-8)
■
BACnet MS/TP
MAC address
: 00 to 7F with rotary switch
Baud rate
: 9600/19.2 k/38.4 k/76.8 kbps
(with rotary switch)
Standard
: Conforms to TIA/EIA-485-A
Transmission distance
: 1500 meters max.
Transmission media
: AWG22 (two shielded twist pair cables)
Character
: 8 data bits, no parity, 1 stop bit
Terminating resistor
: Built-in (ON/OFF setting with DIP switch, factory setting: OFF)
INPUT SPECIFICATIONS
Number of input
: 4
Isolation
: Optical isolator
Input resistance
: Approx. 4.4 kΩ
Common
: 1 common per 4 points (4 terminals)
Contact detecting
: 24 V DC ±10%
ON voltage/ON current
: ≤ 12 V, ≥ 2.5 mA
OFF voltage/OFF current
: ≥ 17 V, ≤ 1.5 mA
ON delay time
: ≤ 2.0 msec.
OFF delay time
: ≤ 2.0 msec.
ON detecting time
: Approx. 5.0 msec.
■
PULSE INPUT SPECIFICATION
Maximum frequency
: 100 Hz
(ON/OFF time ≥ 5 msec.)
Totalized pulse range
: 0 - 4,294,967,295
Max. totalized pulse range
: 1,000 - 4,294,967,295
(Factory setting: 9,999,999)
Count at overflow
: Reset and restart at ‘0'.
OUTPUT SPECIFICATIONS
Number of output
: 4 points
Common
: 1 common per 1 point
Rated load
: 250 V AC @ 2A, 30 V DC @ 2A
Maximum
switching voltage:
250 V AC, 30 V DC
Maximum
switching power
: 500 VA (AC), 60 W (DC)
Minimum applicable load
: 24 V DC @ 5 mA
Relay life
Mechanical
: 2 × 10
7
cycles (180 cycles per min.)
When driving an inductive load, external contact protection and noise quenching recommended.
ON delay time
: ≤ 10 msec.
OFF delay time
: ≤ 10 msec.
Output data update time
: Approx. 300 msec.
INSTALLATION
Power consumption
•
AC
:
Approx. 5 VA at 100 V
Approx. 7 VA at 200 V
Approx. 8 VA at 240 V
Operating temperature
: 0 to 50°C (32 to 122°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE
Battery backup
: RTC (for 7 days max.)
Calendar clock accuracy
: Monthly deviation 2 minutes at 25°C
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (BACnet MS/TP to contact input to contact output to power to FE)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Measurement Category II (contact output)
Installation Category II (power input)
Pollution Degree 2
BACnet MS/TP to contact input to contact output to power:
Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
CONNECTION DIAGRAMS
Tension clamp terminal blocks are used for I/O, power input and connection.
■
COMMON SPECIFICATION
Applicable wire size
: 0.2 − 1.5 mm
2
; stripped length 10 mm
Recommended solderless terminal
• AI0,25-10BU 0.25 mm
2
(Phoenix Contact)
• AI0,34-10TQ 0.34 mm
2
(Phoenix Contact)
• AI0,5-10WH 0.5 mm
2
(Phoenix Contact)
• AI0,75-10GY 0.75 mm
2
(Phoenix Contact)
• A1-10 1.0 mm
2
(Phoenix Contact)
• A1,5-10 1.5 mm
2
(Phoenix Contact)
SUPPORTED BACnet PROPERTY
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.