ES-4827 Rev.11

CRP

Final Control Elements

SERVO-TOP VALVE ACTUATOR TYPE C

(rotary type)
Functions & Features
• Lightweight, compact design
• Simple adjustments
• ISO standard flange
 

MODEL: CRP-[1]1-[2][3][4]

ORDERING INFORMATION

• Code number: CRP-[1]1-[2][3][4]
Specify a code from below for each of [1] through [4].
  (e.g. CRP-241-AB/K)

[1] TORQUE, OPERATION TIME

01: 68.6 N·m, 12 sec./90° (7 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
03: 68.6 N·m, 24 sec./90° (7 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
11: 196 N·m, 12 sec./90° (20 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
13: 196 N·m, 24 sec./90° (20 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
22: 588 N·m, 18 sec./90° (60 kgf·m)
24: 588 N·m, 36 sec./90° (60 kgf·m)

SPAN

1: 45° - 90°

[2] POSITION SETPOINT INPUT

Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

[3] POWER INPUT

AC Power
B: 100 V AC
C: 110 V AC
G: 200 V AC
H: 220 V AC

[4] OPTIONS

Adaptor
blank: without
/K: Adaptor for Kitamura Valve

GENERAL SPECIFICATIONS

Degree of protection: IP55
Action: Direct or reverse; field selectable with DIP switches (factory set to “reverse”)
Operation at abnormally low input: Open, close or stop; field selectable with DIP switches  (factory set to “stop”)
Detectable input drop level: 0.37 ±0.1 V DC; converted into voltage
Wiring conduits: G 1/2 female thread (two)
Terminal board: M3 screw (leadwire size 2 mm2 max.; torque 0.5 N·m)
Housing material: Aluminum alloy
Drive: AC reversible motor (15-minute continuous rating)
Insulation class: E (thermal protector incorporated; 120 ±5°C or 248 ±9°F)
Power control element: Semiconductor switch
Position detection: Potentiometer
Span: 90 degrees (100 degrees max.)
Deadband adjustment: 0.5 – 5.5 % (factory set to approx. 1.5 %)
Re-start limiting timer: Approx. 1.5 seconds
Mechanical limiter: Fixed to 90 degrees position
Isolation: Input or output to power to ground
Zero adjustment: 0 – 25 %
Span adjustment: 50 - 100 %

OUTPUT SPECIFICATIONS

Operation Time & Torque(50 / 60 Hz, with no load)
CRP-221: 18 / 15 sec. ±15 %; 588 N·m (434.0 ft·lbf)
CRP-241: 36 / 30 sec. ±15 %; 588 N·m (434.0 ft·lbf)
Position Signal: 4 – 20 mA DC
Load resistance: ≤ 300 Ω

INSTALLATION

Power input
AC: Operational voltage range: rating ±10 %, 50/60 Hz
Power Consumption
・ Power code B
  CRP-221: 253 VA (50 Hz), 259 VA (60 Hz)
  CRP-241: 215 VA (50 Hz), 198 VA (60 Hz)
・ Power code C
  CRP-221: 303 VA (50 Hz), 273 VA (60 Hz)
  CRP-241: 273 VA (50 Hz), 182 VA (60 Hz)
・ Power code G
  CRP-221: 280 VA (50 Hz), 188 VA (60 Hz)
  CRP-241: 320 VA (50 Hz), 238 VA (60 Hz)
・ Power code H
  CRP-221: 394 VA (50 Hz), 249 VA (60 Hz)
  CRP-241: 425 VA (50 Hz), 291 VA (60 Hz)
Operating temperature: -10 to +50°C (14 to 122 °F)
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: ≤ 2 G (19.6 m/s2)
Mounting position: All directions
Weight: 15 kg (33.1 lb)

PERFORMANCE

Resolution:0.68° (CRP - 22) 0.45°(CRP - 24)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output or power to ground)

FUNCTIONS

Lock Detection
When the valve stroke does not come into deadband range for longer than 2 minutes (approx.) due to motor locking or some other reasons, the CRP stops power supply to the motor.
In order to reset the lock, apply 0 % and 100 % input repeatedly or turn the power supply off and on.
Overload Protection
In order to protect the motor from frequent control operations at high load (load rate ≥ 50 %), the CRP is equipped with a thermal protector in its motor.
When the thermal protector is activated, the motor must be cooled down at least for 30 minutes before restarting.
Electrical Storke Limits
The valve operation can be limited within specific electrical limits without utilizing mechanical limit switches.
Both limits are relative to the operation range adjusted with zero/span adj. The lower limit is fixed to 3.8 mA, while the higher limit is fixed to 20.2 mA.
Manual Operation Handle
The CRP is manual operated in 25 turns.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM