ES-4827 Rev.11
CRP
Final Control Elements
SERVO-TOP VALVE ACTUATOR TYPE C
(rotary type)
Functions & Features
• Lightweight, compact design
• Simple adjustments
• ISO standard flange
MODEL: CRP-[1]1-[2][3][4]
ORDERING INFORMATION
• Code number: CRP-[1]1-[2][3][4]
Specify a code from below for each of [1] through [4].
(e.g. CRP-241-AB/K)
[1] TORQUE, OPERATION TIME
01
: 68.6 N·m, 12 sec./90° (7 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
03
: 68.6 N·m, 24 sec./90° (7 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
11
: 196 N·m, 12 sec./90° (20 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
13
: 196 N·m, 24 sec./90° (20 kgf·m)
(DISCONTINUED; replace with MODEL PRP.)
22
: 588 N·m, 18 sec./90° (60 kgf·m)
24
: 588 N·m, 36 sec./90° (60 kgf·m)
SPAN
1
: 45° - 90°
[2] POSITION SETPOINT INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[3] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
G
: 200 V AC
H
: 220 V AC
[4] OPTIONS
Adaptor
blank
: without
/K
: Adaptor for Kitamura Valve
GENERAL SPECIFICATIONS
Degree of protection
: IP55
Action
: Direct or reverse; field selectable with DIP switches (factory set to “reverse”)
Operation at abnormally low input
: Open, close or stop; field selectable with DIP switches (factory set to “stop”)
Detectable input drop level
: 0.37 ±0.1 V DC; converted into voltage
Wiring conduits
: G 1/2 female thread (two)
Terminal board
: M3 screw (leadwire size 2 mm
2
max.; torque 0.5 N·m)
Housing material
: Aluminum alloy
Drive
: AC reversible motor (15-minute continuous rating)
Insulation class
: E (thermal protector incorporated; 120 ±5°C or 248 ±9°F)
Power control element
: Semiconductor switch
Position detection
: Potentiometer
Span
: 90 degrees (100 degrees max.)
Deadband adjustment
: 0.5 – 5.5 % (factory set to approx. 1.5 %)
Re-start limiting timer
: Approx. 1.5 seconds
Mechanical limiter
: Fixed to 90 degrees position
Isolation
: Input or output to power to ground
Zero adjustment
: 0 – 25 %
Span adjustment
: 50 - 100 %
OUTPUT SPECIFICATIONS
■
Operation Time & Torque(50 / 60 Hz, with no load)
CRP-221: 18 / 15 sec. ±15 %; 588 N·m (434.0 ft·lbf)
CRP-241: 36 / 30 sec. ±15 %; 588 N·m (434.0 ft·lbf)
■
Position Signal
: 4 – 20 mA DC
Load resistance
: ≤ 300 Ω
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %, 50/60 Hz
Power Consumption
・ Power code B
CRP-221: 253 VA (50 Hz), 259 VA (60 Hz)
CRP-241: 215 VA (50 Hz), 198 VA (60 Hz)
・ Power code C
CRP-221: 303 VA (50 Hz), 273 VA (60 Hz)
CRP-241: 273 VA (50 Hz), 182 VA (60 Hz)
・ Power code G
CRP-221: 280 VA (50 Hz), 188 VA (60 Hz)
CRP-241: 320 VA (50 Hz), 238 VA (60 Hz)
・ Power code H
CRP-221: 394 VA (50 Hz), 249 VA (60 Hz)
CRP-241: 425 VA (50 Hz), 291 VA (60 Hz)
Operating temperature:
-10 to +50°C (14 to 122 °F)
Operating humidity
: 30 to 85 %RH (non-condensing)
Vibration
: ≤ 2 G (19.6 m/s
2
)
Mounting position
: All directions
Weight
: 15 kg (33.1 lb)
PERFORMANCE
Resolution
:0.68° (CRP - 22) 0.45°(CRP - 24)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or output or power to ground)
FUNCTIONS
•
Lock Detection
When the valve stroke does not come into deadband range for longer than 2 minutes (approx.) due to motor locking or some other reasons, the CRP stops power supply to the motor.
In order to reset the lock, apply 0 % and 100 % input repeatedly or turn the power supply off and on.
•
Overload Protection
In order to protect the motor from frequent control operations at high load (load rate ≥ 50 %), the CRP is equipped with a thermal protector in its motor.
When the thermal protector is activated, the motor must be cooled down at least for 30 minutes before restarting.
•
Electrical Storke Limits
The valve operation can be limited within specific electrical limits without utilizing mechanical limit switches.
Both limits are relative to the operation range adjusted with zero/span adj. The lower limit is fixed to 3.8 mA, while the higher limit is fixed to 20.2 mA.
•
Manual Operation Handle
The CRP is manual operated in 25 turns.
EXTERNAL DIMENSIONS unit: mm [inch]