ES-1903 Rev.5
CTCS
Plug-in Signal Conditioners M-UNIT
HIGH AC CURRENT TRANSMITTER
(wide bandwidth; clamp-on current sensor)
Functions & Features
• Converts an alternating current into a standard process signal
• Easy-to-install clamp-on type current sensor without needing a current transformer
• Clamp-on current sensor included
• Wide input range from 10 A up to 400 A
• Wide frequency band can be accepted
• Over-voltage clamp element for safety in open circuit
• LCD meter (engineering unit display selectable)
• Simple loop test output (0 % and 100 %)
• High-density mounting
Typical Applications
• Measurement in tight places as never before possible
• Monitoring load current of motors employing inverters
• Detecting failures of a pump or other device by monitoring abnormal load current of motors
• Monitoring current of electric welding machine
MODEL: CTCS–[1][2][3]–[4][5]
ORDERING INFORMATION
• Code number: CTCS-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. CTCS-1100A-C/E2/Q)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] SENSOR
1
: Leadwire type CLSA
2
: Screw terminal type CLSB
[2] INPUT
10
: 0 – 10 A AC
15
: 0 – 15 A AC
20
: 0 – 20 A AC
30
: 0 – 30 A AC
40
: 0 – 40 A AC
50
: 0 – 50 A AC
60
: 0 – 60 A AC
75
: 0 – 75 A AC
100
: 0 – 100 A AC
125
: 0 – 125 A AC
150
: 0 – 150 A AC
175
: 0 – 175 A AC
200
: 0 – 200 A AC
225
: 0 – 225 A AC
250
: 0 – 250 A AC
300
: 0 – 300 A AC
350
: 0 – 350 A AC
400
: 0 – 400 A AC (Not selectable with the sensor
type code 2 'Screw terminal type CLSB')
[3] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 100 Ω min.)
4
: 0 – 10 V DC (Load resistance 1000 Ω min.)
5
: 0 – 5 V DC (Load resistance 500 Ω min.)
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
4W
: -10 – +10 V DC (Load resistance 2000 Ω min.)
5W
: -5 – +5 V DC (Load resistance 1000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[4] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC (Not selectable with Option /E2)
[5] OPTIONS (multiple selections)
Input Signal Indicator
blank
: Without
/E
: With (0.0 - 100.0 % display)
/E2
: With (in engineering unit with backlight and the
simple loop test output)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
ACCESSORIES
The clamp-on current sensor is included in the product package.
■
CLAMP-ON CURRENT SENSOR (leadwire type CLSA)
•
0 – 10 A through 0 – 75 A Use
Sensor model No.
: CLSA-08
Sensor cable model No.
: CLSA-08C-30
Applicable cable diameter
: Max. 10.0
Sensor leadwire
: AWG 22
Weight
: 45 g (1.6 oz)
•
0 – 100 A Use
Sensor model No.
: CLSA-12
Sensor cable model No.
: CLSA-08C-30
Applicable cable diameter
: Max. 16.0
Sensor leadwire
: AWG 22
Weight
: 70 g (2.5 oz)
•
0 – 125 A through 0 – 300 A Use
Sensor model No.
: CLSA-30
Applicable cable diameter: Max
. 24.0
Sensor leadwire
: AWG 18, 200 mm
Weight
: 200 g (7.1 oz)
•
0 – 350 A through 0 – 400 A Use
Sensor model No.
: CLSA-50
Applicable cable diameter
: Max. 36.0
Sensor leadwire
: AWG 18, 200 mm
Weight
: 300 g (10.6 oz)
■
CLAMP-ON CURRENT SENSOR (screw terminal type CLSB)
Connection
: M3 screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Output wiring:
Use AWG22 or thicker wires for the output. Twist the paired wires, extendable up to 30 meters.
•
0 – 10 A through 0 – 50 A Use
Sensor model No.
: CLSB-05
Applicable cable diameter
: Max. 10.0
Weight
: 45 g (1.6 oz)
•
0 – 60 A through 0 – 100 A Use
Sensor model No.
: CLSB-10
Applicable cable diameter
: Max. 16.0
Weight
: 80 g (2.8 oz)
•
0 – 125 A through 0 – 200 A Use
Sensor model No.
: CLSB-20
Applicable cable diameter
: Max. 24.0
Weight
: 200 g (7.1 oz)
•
0 – 225 A through 0 – 350 A Use
Sensor model No.
: CLSB-40
Applicable cable diameter
: Max. 35.0
Weight
: 300 g (10.6 oz)
Note 1: The output values may vary depending on the accuracy of engagement at the clamp connection.
Note 2: The sensor is detachable up to 100 times (approx.).
Note 3: The sensor’s mechanical construction may cause it to generate resonance sound. However, it does not affect the performance of the sensor.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Sensor core to sensor output or input to output to power
Overrange output
: 0 to 120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Simple loop test output
: 0 % and 100 % signal simulated by selecting the front switch positions. (Only for option code /E2)
■ DISPLAY (Input indicator)
• Option code: /E
LCD digital display
: 0.0 - 100.0 % (min. digit 0.1 %)
(No scaling)
• Option code: /E2
LCD digital display
: Engineering unit
Display scaling
: -10000 – +10000
Decimal position
: 10
-1
- 10
-4
or no decimal point
Engineering unit
: %, μV, mV, V, mA, A, °C, °F, Ω, DEG K, mHz, Hz, kHz, VAC, AAC, mg, g, kg, t, rpm or rps selectable
Back light
: Green at normal, red at loop test output enable
Factory setting
: scaling 0.00 - 100.00, unit: %
INPUT SPECIFICATIONS
Frequency
: 4 Hz – 10 kHz
Overload capacity
CLSA - 08
: 120 A continuous
CLSA - 12
: 300 A continuous
CLSA - 30
: 360 A continuous
CLSA - 50
: 600 A continuous
CLSB - 05
: 100 A continuous
CLSB - 10
: 200 A continuous
CLSB - 20
: 300 A continuous
CLSB - 40
: 600 A continuous
Operational range
: 0 – 120 % of rating
Be sure that the input voltage is of 440 V or less.
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
•
DC
: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.) approx. 2 W (80 mA at 24 V; approx. 3 W with Option /E2)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (Except clamp-on current sensor)
PERFORMANCE in percentage of span
Accuracy
: ±1.5 % (20 – 500 Hz)
Display accuracy
: ± (1.5 % of FS + 1 digit)
Simple loop test output setting accuracy
: ±0.5 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Ripple
: 0.5 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute
(input to output to power to ground)
1000 V AC @1 minute
(sensor core to sensor output)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
■ Sensor model No.: CLSA-08
■ Sensor model No.: CLSA-12
■ Sensor model No.: CLSA-30
■ Sensor model No.: CLSA-50
■ Sensor model No.: CLSB-05
■ Sensor model No.: CLSB-10
■ Sensor model No.: CLSB-20
■ Sensor model No.: CLSB-40