ES-1395 Rev.15

DA3

Plug-in Signal Conditioners M-UNIT

D/A CONVERTER

(16-bit resolution)
Functions & Features
• Converts parallel digital signal into a DC output
• BCD, binary, offset binary, two's complement, reflected binary inputs
• Positive or negative logic selectable
• Display can be scaled in convenient engineering unit
• Scalable DC output range
• Parity check
Typical Applications
• Interface of analog signal for computers and PLC
 

MODEL: DA3–[1][2]–[3][4]

ORDERING INFORMATION

• Code number: DA3-[1][2]-[3][4]
  Specify a code from below for each of [1] through [4].
  (e.g. DA3-V11-M2/A/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)
Use Ordering Information Sheet (No. ESU-1395) for specifying programmable variables. Default setting will be used if not specified.

[1] OUTPUT

Current
Z1: Range 0 – 20 mA DC (Load resistance 600Ω max.)
Voltage
V1: Range -1 – +1 V DC (Load resistance 1000Ω min.)
V2: Range -10 – +10 V DC (Load resistance 10kΩ min.)

[2] RESPONSE TIME

1: 400 msec.
2: 10 msec.

[3] POWER INPUT

AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)
DC Power
R3: 12 – 24 V DC
(Operational voltage range 10.8 - 26.4 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[4] OPTIONS (multiple selections)

Input
Blank: TTL level
/A: 24 V DC
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable (model: MCN26)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
Input:
26-pin connector(OMRON XG4A-2634)
  Paired connector: OMRON XG4M-2630-T, XG5M-263x-N
  Cover: OMRON XG5S-2612 
Output, power:
M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -15 to +115 %
DISPLAY
LED
: 7 mm (.28") 7 segment, red
Number of display digits: 4 digits for DATA display; 2 digits for ITEM display
PV indication: Input signal in engineering unit
Overrange indication: LEDs blinking
Power saving mode: Displays turn off if the keys are untouched for a preset time period
PL1 (POL) LED: Red LED turns on at negative polarity.
PL2 (LOAD) LED: Red LED turns on at LOAD.
Setting: Via the front key pad
• Display range scaling
• Available number of bits
• Data input logic
• POL input
• LOAD input
• Parity check
For detailed information, refer to the instruction manual.

INPUT SPECIFICATIONS

■ Input Code: Code, logic and scaling are user-selectable.
 BCD with polarity (Settable range: -9999 - 9999)
 Binary with polarity (Settable range: -7FFF - 7FFF)
 Offset binary (Settable range: 0000 - FFFF)
 Two’s complement (Settable range: 8000 - 7FFF)
 Reflected binary (Settable range: 0000 - FFFF)
Output code, logic, scaling are settable.
Available number of bits
Selectable from 8, 10, 12, 14, 16 bits
■ Input Specifications
• TTL Level:
TTL level (5 V-CMOS level) or open
collector (sink type), dry contact(detecting voltage: approx. 5 V, saturation voltage: ≤ 1 V, sink current: 1 mA)
Saturation voltage: ≤ 1 V
Sink current: 1 mA
Common: Negative
• 24 V DC: Open collector (source type)
Rated voltage: 24 V DC ±10%, ripple 5 %p-p max.
ON voltage/current: ≥ 18 V / 2.5 mA DC
OFF voltage/current: ≤ 3 V / 0.4 mA DC
Input current: ≤ 3.5 mA @24 V DC
Input resistance: Approx. 7.5 kΩ
Common: Negative
POL input (Polarity): Same logic and level as for the
input code; logic user-selectable
■ LOAD input: Same logic and level as for the
input code; logic user-selectable
Odd or even parity: Same logic and level as for the
input code; logic user-selectable

OUTPUT SPECIFICATIONS

DC Current: 0 – 20 mA DC
Operational range: 0 – 24.0 mA DC
Minimum increment: 0.1 mA
DC Voltage
Code V1: -1.00 – +1.00 V DC
  Operational range: -1.15 – +1.15 V DC
  Minimum increment: 10 mV
Code V2: -10.0 – +10.0 V DC
  Operational range: -11.5 – +11.5 V DC
  Minimum increment: 100 mV

INSTALLATION

Power consumption
AC: Approx. 10 VA
DC: Approx. 4 W (160 mA at 24 V)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 300 g (0.66 lb)

PERFORMANCE in percentage of max. span

Accuracy: ±0.1 %
Min. span required to ensure the accuracy: 20 % of the nominal output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Resolution: 16 bits
Response time: ≤ 400 msec. or ≤ 10 msec. (0 – 90 %)
as specified by model suffix code, with ITEM 16 set to 0.0.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Input or output to power: Reinforced insulation (300 V)
  Input to output: Basic insulation (300 V)
RoHS Directive

EXTERNAL VIEW

PARAMETER LIST

It is available to configure or confirm settings shown below by using front key pad.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT CONNECTOR (26-pin)

TIMING CHART

INPUT-OUTPUT RELATION EXAMPLES

• FS
-FS stands for -15 % of the input range (0 to 100 %), which is configured by ITEM 08, display range scaling 0 % and ITEM 09, display range scaling 100 %. +FS stands for +115 % of the input range.

• OR
When one of the following conditions is true, the digital input overflows (OR).
 1) When the input signal is out of the range between -FS and +FS.
 2) When the display value (= input signal) exceeds the display range.
 The display range differs according to input code. For example, in case of BCD with polarity, it is -9999 to 9999. Please refer to the instruction manual for detail.