ES-1338 Rev.10
DR
Plug-in Signal Conditioners M-UNIT
DIFFERENTIAL RTD TRANSMITTER
(non-isolated)
Functions & Features
• Providing a DC output in proportion to the temperature difference between two RTDs
• LCD meter (engineering unit display selectable)
• Simple loop test output (0 % and 100 %)
• High-density mounting
Typical Applications
• Measuring temperature difference between the inlet and outlet of a heat exchanger
• Coolant
• Power plant
MODEL: DR–[1]–[2][3]
ORDERING INFORMATION
• Code number: DR-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. DR-A-B/E2/Q)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
INPUT (2-wire RTDs, dual input)
JPt100 (JIS'89) or Pt100 (JIS'97, IEC)
Pt100 (JIS ’89) is deviated from Pt100
(JIS ’97) only within the described accuracy.
[1] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 100 Ω min.)
4
: 0 – 10 V DC (Load resistance 1000 Ω min.)
5
: 0 – 5 V DC (Load resistance 500 Ω min.)
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[2] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC (Not selectable with Option /E2.)
[3] OPTIONS (multiple selections)
LCD Meter (for indicating temperature difference)
blank
: Without
/E
: With (0.0 - 100.0 % display)
/E2
: With (in engineering unit with backlight and the
simple loop test output)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input or output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Simple loop test output
: 0 % and 100 % signal simulated by selecting the front switch positions. (Only for option code /E2)
■
DISPLAY (LCD meter)
• Option code: /E
LCD digital display
: 0.0 - 100.0 % (min. digit 0.1 %)
(No scaling)
• Option code: /E2
LCD digital display
: Engineering unit
Display scaling
: -10000 – +10000
Decimal position
: 10
-1
- 10
-4
or no decimal point
Engineering unit
: %, μV, mV, V, mA, A, °C, °F, Ω, DEG K, mHz, Hz, kHz, VAC, AAC, mg, g, kg, t, rpm or rps selectable
Back light
: Green at normal, red at loop test output enable
Factory setting
: scaling 0.00 - 100.00, unit: %
INPUT SPECIFICATIONS
Input
: 2-wire RTDs (two)
Maximum leadwire resistance
: Difference 0.5 Ω maximum between the transmitter and each RTD; each leadwire resistance 10 Ω or less
Sensing current
: 2 mA
Difference range
: 0 – 20°C or 0 – 36°F (fixed)
Temperature range
: 0 – 50°C or 32 – 122°F (fixed)
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %, 50/60 ±2 Hz, approx. 2 VA
(approx. 3 VA with Option /E2)
•
DC
: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.) approx. 2 W (80 mA at 24 V; approx. 3 W with Option /E2)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 % (Temperature within 15 – 35°C or 59 – 95°F)
Display accuracy
: ± (0.2 % of FS + 1 digit)
(Temperature within 15 – 35°C or 59 – 95°F)
Simple loop test output setting accuracy
: ±0.5 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input or output to power to ground)