ES-1472 Rev.13
FJFX
Space-saving Plug-in Signal Conditioners F-UNIT
LINEARIZER
(field-programmable)
Functions & Features
• Accepting non-linear input and providing a linearized output, proportional to the process variables
• Micro-processor based
• On-site calibration up to 16 points using a hand-held programmer PU-2x
• Field-programmable input range
• High-density mounting
Typical Applications
• V-notch weir
• Gas analyzer
• Irregular-shaped tank level input for volume calculation
MODEL: FJFX–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: FJFX-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. FJFX-6A-L/Q)
• Special input range (For codes U1, U2 & U3)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1669) to specify linearization data when the I/O signals are nonlinear.
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
H
: 10 – 50 mA DC (Input resistance 100 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
U1
: Range ±100 mV;
(Minimum span 3 mV, Input resistance 20 kΩ min.)
U2
: Range ±1000 mV;
(Minimum span 30 mV, Input resistance 20 kΩ min.)
U3
: Range ±10 V;
(Minimum span 0.3 V,Input resistance 1 MΩ min.)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
[3] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L
: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Linearization
: 16 points max. within the range of -15.00 – +115.00 % input or output; represented as percentage of full-scale
Adjustments
: Programming Unit (model: PU-2x)
(Refer to the users manual of JXCON for the adjustments configurable with JXCON.)
• Linearization data
• Input range
• Zero and span
• Simulating output
• Others
Input range can be changed with Codes U1, U2 or U3 and limited within ranges of each code type.
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
■
DC Voltage
: -10 – +10 V DC
Minimum span
: 3 mV
Offset
: Max. 3 times span
Input
resistance
(Input Range: Input Resistance)
U1
: ±100 mV
U2
: ±1000 mV
U3
: ±10 V
Default setting will be used if not otherwise specified.
U1
: 0 – 100 mV DC
U2
: 0 – 1 V DC
U3
: 0 – 10 V DC
INSTALLATION
Power input
•
AC
: Approx. 4.5 VA
•
DC
: 24 V approx. 70 mA
110 V approx. 20 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail; Standard Rack Mounting Frame BX-16H available
Weight
: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain] with segment gain > 1
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
Power input code R
:
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
500 V AC @ 1 minute (I/O to power)
Power input code K, L, P
:
1000 V AC @ 1 minute (input to output)
2000 V AC @ 1 minute (input or output or power to ground)
1500 V AC @ 1 minute (I/O to power)
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM