ES-9041 Rev.4

JC-HL

Remote I/O JC Series

HUB MODULE

 

MODEL: JC–HL-[1]-1[2]-[3][4]

ORDERING INFORMATION

• Code number: JC-HL-[1]-1[2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. JC-HL-7-12-R/H/Q)
• Specify the specification for option code /Q
  (e.g. /SET)

[1] I/O TYPE

3: 3 port (trunk 1 port, feeder 2 port)
7: 7 port (trunk 1 port, feeder 6 port)

TERMINAL BLOCK

1: Tension clamp terminal block for power supply
   RJ-45 Modular jack for communication

[2] COMMUNICATION CONNECTOR PIN ASSIGNMENT

1: 3, 4 - 5, 6 pair wiring
  (The HLS related products standard pin assignment)
2: 4, 5 - 3, 6 pair wiring
  (Ethernet LAN cable pin assignment)

[3] POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R5: 16 - 32 V DC
(Operational voltage range 15 - 33 V DC, ripple 10 %p-p max.)

[4] OPTIONS (multiple selections)

Communication Mode
blank: Full-duplex
/H: Half-duplex
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-9041)

FUNCTIONS & FEATURES

The HUB Module for HLS (model: JC-HL) extends total length of network cable and branch cable of HLS (Hi-speed Link System). Total max. length is 2.4 km when transfer rate is 3 Mbps. In order to connect the JC-HL, the master unit configuring HLS must support HUB module.

HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.

RELATED PRODUCTS

• High-speed link system I/O modules (model: R7F4DH, R7K4DH, R7HL, R7FN etc.)
• MP2200/MP2300 series use HLS master module (model: MPHLS)

GENERAL SPECIFICATIONS

Number of port:
JC-HL-3: Trunk 1 port, feeder 2 port
JC-HL-7: Trunk 1 port, feeder 6 port
Max. number of inserted HUBs: 7 
(Depending on specification of master unit)
Connectable devices: The products conforming to HLS
Connection
  Network: RJ-45 Modular Jack 
  Power input: Separable tension clamp terminal
Power on LED: PWR (green) turns on while the power is supplied.

HLS COMMUNICATION

Communication mode: Full-duplex or half-duplex
Network cable
• Shield cable
ZHY262PS (Shinko Seisen Industry Co., Ltd.)
ZHT262PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance / Transfer rate:
Refer to the table below (Selectable with
DIP switch. Factory default: 12 Mbps)
Terminating resistor:
Trunk built-in (Selectable with DIP switch. Factory default: disable)
Feeder built-in
Status indicator LEDs: ERR, LNK
(Refer to the instruction manual for details)

INSTALLATION

Rated current for power supply connector: 8A
Power consumtpion:
  JC-HL-3: Approx. 1 W
  JC-HL-7: Approx. 1.4 W
Operating temperature: -10 to +55°C
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight
  JC-HL-3: 150 g (0.33 lb)
  JC-HL-7: 160 g (0.35 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
JC-HL-3 (HLS0A or HLS0B to HLS1 or HLS2 or FE to power)
JC-HL-7 (HLS0A or HLS0B to HLS1 or HLS2 or HLS3 or HLS4 or HLS5 or HLS6 or FE to power)
Dielectric strength: 1500 V AC @ 1 minute
JC-HL-3 (HLS0A or HLS0B to HLS1 or HLS2 or FE to power)
JC-HL-7 (HLS0A or HLS0B to HLS1 or HLS2 or HLS3 or HLS4 or HLS5 or HLS6 or FE to power)

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

MOUNTING REQUIREMENTS unit: mm (inch)

EXTERNAL VIEW

CONNECTION DIAGRAMS

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.