ES-1670 Rev.12
JS
Plug-in Signal Conditioners M-UNIT
SELF-SYNCH TRANSMITTER
(field-programmable)
Functions & Features
• Converting position signal from a self-synchronizing motor into DC signal proportional to the rotating shaft position
• Micro-processor based
• Linearization
• Loop testing via hand-held programmer PU-2x
• Offset adjustable via front multi-turn screwdriver adjustment
• High-density mounting
Typical Applications
• Position indicator using self-synch
• Tank gauge
• Sounding level meter
MODEL: JS-1[1]-[2][3]
ORDERING INFORMATION
• Code number: JS-1[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. JS-1A-B/Q)
• Input range (e.g. 270°)
• Special output ranges (For codes Z & 0)
• Linearization data (max. 16 points)
Use Ordering Information Sheet (No. ESU-1669) to specify linearization data when the I/O signals are nonlinear.
• Specify the specification for option code /Q
(e.g. /C01/S01)
INPUT
1
: Self-synch signal
[1] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W
: -5 – +5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[2] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Offset adjustment
: 0 to 360°(front)
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Linearization
: 16 points max. within the range of -15.00 – +115.00 % input or output; represented as percentage of full-scale
Adjustments
: Programming Unit (model: PU-2x); input range, offset, linearization data, zero and span, input angle & coordinates, etc.
(Refer to the users manual of JXCON for the adjustments configurable with JXCON.)
INPUT SPECIFICATIONS
Input
: Self-synch signal
Measurement range
: 0 – 360°
Input range
: 60 – 360° (270° for default)
Input resistance
: 1 MΩ min.
Rated input voltage
: 90 V AC
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +20 V DC
Span:
Min. 5 mV, max. 20 V
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 % or ±0.5°, whichever is greater (gain ≤ 1)
accuracy = [±0.2 %(±0.5°) × gain] with the gain > 1
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: Approx. 2 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)