ES-3606 Rev.7
KS2TR2
Plug-in Signal Conditioners K-UNIT
TEMPERATURE INPUT LIMIT ALARM
(digital adjustments; dual alarm trip)
Functions & Features
• Providing relay contact closures at preset DC input levels
• Dual (Hi/Lo) trip
• Front digital displays
• Programmable with front keys
Typical Applications
• Various alarm applications
MODEL: KS2TR2–1–[1][2]
ORDERING INFORMATION
• Code number: KS2TR2-1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. KS2TR2-1-R/Q)
• Specify the specification for option code /Q
(e.g. /SET)
TEMPERATURE INPUT
Thermocouple input
K(CA), E(CRC), J(IC), T(CC), B(RH), R, S, P(Platinel Ⅱ),
C(WRe 5-26), N
RTD input
JPt 100 (JIS ’89) , Pt 100 (JIS ’97, IEC)
OUTPUT
1
: Relay; SPDT or transfer contact
[1] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-3606)
GENERAL SPECIFICATIONS
Construction
: Panel flush mounting, plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to SET1 to SET2 to power
Time constant for the input filter (P-dF):
5.0 to 900.0 sec. (0 – 63 %)
Alarm relay switching delay time (P-d1, P-d2):
1 to 10 sec.; programmable independently for each setpoint
Programming:
Front key
Setpoint adjustment (ST1, ST2):
-5 to +105 %; programmable independently for each setpoint
Deadband (hysteresis) (HYS1, HYS2)
: 0 – 102 %; programmable independently for each setpoint
Burnout
: Upscale or downscale or no burnout
Cold junction compensation (CJM):
ON or OFF; for
thermocouple input only; CJC sensor incorporated
Power ON delay (P-d0):
0 to 20 sec.
Read rate:
0.5 sec.
Temperature unit (P-F):
°C, °F
Alarm mode (P-A1, P-A2):
Programmable independently for each setpoint; See Table below.
DISPLAY
Display
: 4 digits of 10 mm (.39”) height, 7-segment LED
Scaling range
: -1999 to 9999 counts
Measured Value (PV)/Alarm (SET1) display
: Red LEDs
Alarm (SET2) parameter display
: Green LEDs
PV display at abnormal input
: Over range or under range displayed
Front LEDs
Power indicator
: Green LED turns on while the power is turned on.
Measured Value (PV) indicator
: Green LED turns on when PV display is set.
Alarm SET1 indicator
: Red LED turns on when the Alarm SET1 is in tripped conditions.
Alarm SET2 Indicator
: Red LED turns on when the Alarm SET2 is in tripped conditions.
Engineering unit indication
: Sticker label attached; ℃, °F, etc.
INPUT SPECIFICATIONS
• Thermocouple
Thermocouple type and temperature range
J (IC) : (0 to 400°C or 32 to 752°F)
J (IC) : (0 to 800°C or 32 to 1472°F)
K (CA) : (0 to 400°C or 32 to 752°F)
K (CA) : (0 to 800°C or 32 to 1472°F)
K (CA) : (0 to 1200°C or 32 to 2192°F)
R : (0 to 1600°C or 32 to 2912°F)
B (RH) : (0 to 1800°C or 32 to 3272°F)
S : (0 to 1600°C or 32 to 2912°F)
T (CC) : (-199 to 200°C or -328 to 392°F)
T (CC) : (-150 to 400°C or -238 to 752°F)
E (CRC) : (0 to 800°C or 32 to 1472°F)
E (CRC) : (-199 to 800°C or -328 to 1472°F)
N : (0 to 1300°C or 32 to 2372°F)
P (Platinel Ⅱ) : (0 to 1300°C or 32 to 2372°F)
C (WRe 5-26) : (0 to 2300°C or 32 to 4172°F)
Input resistance:
≥ 1 MΩ
Burnout sensing:
Approx. 0.3 μA
■
RTD
RTD type and temperature range:
Pt 100 (JIS '97, IEC): (-150 to +850°C or -238 to +1562°F)
JPt 100 (JIS '89): (-150 to +600°C or -238 to +1112°F)
Sensing current
: Approx. 0.3 mA
Maximum leadwire resistance
: 20 Ω per wire
OUTPUT SPECIFICATIONS
■ Relay Contact: SPDT relays
220 V AC @3 A (cos ø = 1)
30 V DC @3 A (resistive load)
Caution: N.O. and N.C. contacts could be conductive at the same time. DO NOT connect both contacts at the same time.
Maximum switching voltage: 220 V AC or 30 V DC
Maximum switching power: 660 VA or 90 W
Minimum load: 10 V DC @1 mA
Mechanical life: 2 × 107 cycles with no loads
For maximum relay life with inductive loads, external protection is recommended.
INSTALLATION
Power consumption
•
AC
:
≤ 5 VA at 100 V
≤ 6 VA at 200 V
≤ 6 VA at 264 V
•
DC
: ≤ 2.5 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting:
Panel flush mounting with attached
mounting bracket, surface or DIN rail
Weight
: 200 g (0.44 lb)
PERFORMANCE
Display accuracy
•Thermocouple
: ±0.5 % FS ± 1 digit ± 3°C (5.4°F)
±1 % FS ± 1 digit ± 3°C (5.4°F) for T, E (≤ -100°C, ≤ -148 °F)
±5 % FS ± 1 digit ± 3°C (5.4°F) for B (0 – 500°C, 32 – 932°F)
±1 % FS ± 1 digit ± 3°C (5.4°F) for R (0 – 400°C, 32 – 752°F)
(In case of type B thermocouple the accuracy near 0°C may be degraded due to the characteristic of the sensor.)
•
RTD
: ±0.5 % FS ± 1 digit
Setpoint accuracy:
Display accuracy ± 0.1 % FS
Trip point repeatability:
Included in the setpoint accuracy
Cold junction compensation error
: ±3°C at 25 ±5°C (±5.4°F at 77 ±9°F)
Burnout response
: Approx. 10 sec.
Line voltage effect
: Included in the display accuracy
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @1 minute
(input to SET1 or SET2 to power)
500 V AC @1 minute (SET1 to SET2)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II (power)
Measurement Category II (output)
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
PANEL CUTOUT unit: mm
■PANEL CUTOUT
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM