ES-3603 Rev.6
KS2V3
Plug-in Signal Conditioners K-UNIT
DC INPUT LIMIT ALARM
(digital adjustments; dual alarm trip; w/o burnout)
Functions & Features
• Providing relay contact closures at preset DC input levels
• Dual (Hi/Lo) trip
• Front digital displays
• Programmable with front keys
• Alarm relay switching delay time 999 sec. max.
Typical Applications
• Various alarm applications
MODEL: KS2V3–61–[1][2]
ORDERING INFORMATION
• Code number: KS2V3-61-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. KS2V3-61-R/Q)
• Specify the specification for option code /Q
(e.g. /SET)
INPUT
Voltage
6
: 1 – 5 V DC
(Use a resistor module for current input)
OUTPUT
1
: Relay; SPDT or transfer contact
[1] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-3603)
RELATED PRODUCTS
• Resistor module (model: REM)
500 Ω for 2 – 10 mA DC
250 Ω for 4 – 20 mA DC
100 Ω for 10 – 50 mA DC
GENERAL SPECIFICATIONS
Construction
: Panel flush mounting, plug-in
Connection
: M3.5 screw terminals
Screw terminal:
Chromated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to SET1 to SET2 to power
Time constant for the input filter (P-dF):
0.0 to 900.0 sec. (0 – 63 %)
Alarm relay switching delay time (P-d1, P-d2):
1 to 999 sec.; programmable independently for each setpoint
Programming:
Front key
Setpoint adjustment (ST1, ST2):
-5 to +105 %; programmable independently for each setpoint
Deadband (hysteresis) (HYS1, HYS2)
: 0 – 102 %; programmable independently for each setpoint
Power ON delay (P-d0):
0 to 20 sec.
Read rate:
0.5 sec.
Alarm mode (P-A1, P-A2):
Programmable independently for each setpoint; See Table below.
DISPLAY
Display
: 4 digits of 10 mm (.39”) height, 7-segment LED
Scaling range
: -1999 to 9999 counts
Measured Value (PV)/Alarm (SET1) display
: Red LEDs
Alarm (SET2) parameter display
: Green LEDs
PV display at abnormal input
: Over range or under range displayed
Front LEDs
Power indicator
: Green LED turns on while the power is turned on.
Measured Value (PV) indicator
: Green LED turns on when PV display is set.
Alarm SET1 indicator
: Red LED turns on when the Alarm SET1 is in tripped conditions.
Alarm SET2 Indicator
: Red LED turns on when the Alarm SET2 is in tripped conditions.
Engineering unit indication
: Sticker label attached;
DC, AC, W, °C, °F, V, mV, A, mA, %, kW, mW,
kV, kA, kvar, Mvar, var, m, mm, kg, kg/h,
kPa, MPa, N·m, Nm
3
/h, m
3
/h, m
3
/sec, m/sec,
ℓ/min, %RH, ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa.
INPUT SPECIFICATIONS
■
DC Voltage
: -5 – +105 %
Input resistance
: ≥ 1 MΩ
OUTPUT SPECIFICATIONS
■
Relay Contact:
SPDT relays
220 V AC @3 A (cos ø = 1)
30 V DC @3 A (resistive load)
Caution: N.O. and N.C. contacts could be conductive at the same time. DO NOT connect both contacts at the same time.
Maximum switching voltage:
220 V AC or 30 V DC
Maximum switching power:
660 VA or 90 W
Minimum load:
10 V DC @1 mA
Mechanical life:
2 × 10
7
cycles with no loads
For maximum relay life with inductive loads, external protection is recommended.
INSTALLATION
Power consumption
•
AC
:
Approx. 3.1 VA at 100 V
Approx. 4.1 VA at 200 V
Approx. 4.8 VA at 264 V
•
DC
: Approx. 1.7 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting:
Panel flush mounting with attached
mounting bracket, surface or DIN rail
Weight
: 200 g (0.44 lb)
PERFORMANCE
Display accuracy:
±0.5% FS ±1 digit
Setpoint accuracy:
Display accuracy ± 0.1 % FS
Trip point repeatability:
Included in the setpoint accuracy
Line voltage effect
: Included in the display accuracy
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @1 minute
(input to SET1 or SET2 to power)
500 V AC @1 minute (SET1 to SET2)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II (power)
Measurement Category II (output)
Pollution Degree 2
Input to output to power: Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
PANEL CUTOUT unit: mm
■PANEL CUTOUT
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM