ES-3520 Rev.7
KWMS2
Plug-in Signal Conditioners K-UNIT
POTENTIOMETER TRANSMITTER
(CE, two isolated outputs)
Functions & Features
• Providing two DC outputs proportional to a potentiometer or slidewire position input
• Constant voltage excitation allows the connection of pots with total resistance from 100 Ω – 10 kΩ without affecting accuracy
• 50 % zero/span adjustments with minimal interaction
• Fast response type available
• High-density mounting
Typical Applications
• Tank levels
• Positions
MODEL: KWMS2–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: KWMS2-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. KWMS2-A6-H/K/Q)
• Special output ranges (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Note: When the user requires a current and a voltage output, specify the current to be the Output 1 which allows a greater load.
INPUT POTENTIOMETER
Total resistance 100 Ω – 10 kΩ
[1] OUTPUT 1
Current
A
: 4 – 20 mA DC (Load resistance 600 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1200 Ω max.)
C
: 1 – 5 mA DC (Load resistance 2400 Ω max.)
D
: 0 – 20 mA DC (Load resistance 600 Ω max.)
E
: 0 – 16 mA DC (Load resistance 750 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1200 Ω max.)
G
: 0 – 1 mA DC (Load resistance 12 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 10 kΩ min.)
5W
: -5 – +5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[2] OUTPUT 2
Current
A
: 4 – 20 mA DC (Load resistance 350 Ω max.)
B
: 2 – 10 mA DC (Load resistance 700 Ω max.)
C
: 1 – 5 mA DC (Load resistance 1400 Ω max.)
D
: 0 – 20 mA DC (Load resistance 350 Ω max.)
E
: 0 – 16 mA DC(Load resistance 430 Ω max.)
F
: 0 – 10 mA DC (Load resistance 700 Ω max.)
G
: 0 – 1 mA DC (Load resistance 7000 Ω max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
Same range availability as Output 1
[3] POWER INPUT
AC Power
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
[4] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank
: Standard (≤ 0.5 sec.)
/K
: Fast Response (Approx. 25 msec.)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to power
Zero adjustment
: 0 – 50 % of total resistance (front)
Span adjustment
: 50 – 100 % of total resistance (front)
INPUT SPECIFICATIONS
Minimum span
: 50 % of total resistance
Excitation
: 0.5 V DC
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 12 V max. for Output 1;
7 V max. for Output 2
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max. at ≥ 0.5 V
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
•
DC
: Operational voltage range: rating ±10 %
ripple 10 %p-p max., approx. 3 W (125 mA at 24 V)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (0.88 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2300 V AC @ 1 minute
(input or output to power to ground)
1350 V AC @ 1 minute (input to output)
1000 V AC @ 1 minute (output 1 to output 2)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM