ES-3512 Rev.7
KYV
Plug-in Signal Conditioners K-UNIT
ISOLATOR
Functions & Features
• Standard instrumentation signal isolator
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Isolation between control room and field instrumentation
MODEL: KYV–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: KYV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. KYV-6A-B/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
Voltage
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
[3] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (0.88 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM