ES-3512 Rev.7

KYV

Plug-in Signal Conditioners K-UNIT

ISOLATOR

Functions & Features
• Standard instrumentation signal isolator
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Isolation between control room and field instrumentation
 

MODEL: KYV–[1][2]–[3][4]

ORDERING INFORMATION

• Code number: KYV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. KYV-6A-B/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

[2] OUTPUT

Current
A: 4 – 20 mA DC (Load resistance 750 Ω max.)
Voltage
6: 1 – 5 V DC (Load resistance 500 Ω min.)

[3] POWER INPUT

AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS

DC Current:
Shunt resistor attached to the input terminals (0.5 W)

INSTALLATION

Power input
AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

EXTERNAL DIMENSIONS unit: mm [inch]

TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM