ES-5005 Rev.15
M2BS-16
Super-mini Signal Conditioners Mini-M Series
INSTALLATION BASE (16 positions)
Functions & Features
• Receiving at the maximum of 16 modules of Mini-M series signal conditioners
• Screw terminal or connector output
• Power supplied through printed wiring on the base
MODEL: M2BS–16[1][2]
ORDERING INFORMATION
• Code number: M2BS-16[1][2]
Specify a code from below for each of [1] and [2].
(e.g. M2BS-16U2/D/UL)
[1] FUNCTION
U0
: Screw terminal block
U1
: Fujitsu FCN type I/O connector (UL not available)
U2
: Omron I/O connector
[2] OPTIONS (multiple selections)
Mounting
blank
: Surface
/D
: DIN rail mounting adaptor (Not selectable for M2BS-16U0)
Standards & Approvals
blank
: CE marking
/UK
: CE, UKCA marking
/UL
: UL approval, CE marking
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Capacity
: 16 positions
Connection
Power input
: M3 screw terminals (torque 0.8 N·m)
Input and output
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
INSTALLATION
Power input
: Refer to signal conditioner data sheet. Choose the same power input specification for all units.
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface; optional DIN rail mounting available
for M2BS-16U1, U2 (in horizontal direction only)
Weight
: 1.8 kg (4.0 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
(input to output to power to FG)
Dielectric strength
: 2000 V AC @1 minute (input to output to power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
UK conformity (UKCA):
The UK legislations and designated standards are equivalent to the applicable EU directives.
(Refer to our website for more information about the legislations and designated standards.)
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 3111-1, CAN/CSA-C22.2 No.1010-1)
Voltage at the field I/O terminals (except power input terminals) limited within 30 V DC for UL.
CONNECTION DIAGRAM
■ MODEL: M2BS-16U0 (screw terminal block)
■ CONNECTION DIAGRAM
■ MODEL: M2BS-16U1 (Fujitsu FCN type I/O connector)
■ CONNECTION DIAGRAM
■ MODEL: M2BS-16U2 (Omron I/O connector)
■ CONNECTION DIAGRAM
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
■ M2BS-16U0
■ M2BS-16U1, U2
MOUNTING REQUIREMENTS unit: mm [inch]
■ M2BS-16U0
■ M2BS-16U1, U2