ES-5006 Rev.13

M2BS-8

Super-mini Signal Conditioners Mini-M Series

INSTALLATION BASE (8 positions)

Functions & Features
• Receiving at the maximum of 8 modules of Mini-M series signal conditioners
• Connector output
• Power supplied through printed wiring on the base

MODEL: M2BS–8[1][2]

ORDERING INFORMATION

• Code number: M2BS-8[1][2]
Specify a code from below for each of [1] and [2].
   (e.g. M2BS-8U2/D/UL)

[1] FUNCTION

U1: Fujitsu FCN type I/O connector  (UL not available)
U2: Omron I/O connector

[2] OPTIONS (multiple selections)

Mounting
blank: Surface
/D: DIN rail mounting adaptor
Standards & Approvals
blank: Without UL
/UL: UL approval

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Capacity: 8 positions
Connection
  Power input
: M3 screw terminals (torque 0.8 N·m)
  Input and output: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel

INSTALLATION

Power input: Refer to signal conditioner data sheet.  Choose the same power input specification for all units.
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: wall; optional DIN rail mounting available
(in horizontal direction only)
Weight: 780 g (1.72 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
(input to output to power to FG)
Dielectric strength: 2000 V AC @1 minute  (input to output to power to FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Input or output to power: Reinforced insulation (300 V)
  Input to output: Basic insulation (300 V)
RoHS Directive
Approval:
UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
  (UL 3111-1, CAN/CSA-C22.2 No.1010-1)
Voltage at the field I/O terminals (except power input terminals) limited within 30 V DC for UL.

CONNECTION DIAGRAM

■ MODEL: M2BS-8U1 (Fujitsu FCN type I/O connector)
■ CONNECTION DIAGRAM
■ MODEL: M2BS-8U2 (Omron I/O connector)
■ CONNECTION DIAGRAM

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]