ES-5027 Rev.11

M2DYH

Super-mini Signal Conditioners Mini-M Series

CURRENT LOOP SUPPLY

(applicable to HART signal)
Functions & Features
• Powers a 4 – 20 mA DC current loop
• Isolates and relays HART signals
• Shortcircuit protection
• Applicable to smart transmitters
Typical Applications
• 2-wire HART transmitters

MODEL: M2DYH–24A–[1][2]

ORDERING INFORMATION

• Code number: M2DYH-24A-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. M2DYH-24A-M2/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

SUPPLY OUTPUT

24: 24 V DC

INPUT

Current
4 – 20 mA DC (Input resistance 250 Ω)

OUTPUT

Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)

[1] POWER INPUT

AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
/C04: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +110 %
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

SUPPLY OUTPUT

(across the terminals 1 – 5)
Output voltage: 24 – 28 V DC with no load
18 V DC min. at 20 mA
Current rating: ≤ 22 mA DC
Shortcircuit Protection
Current limited
: 30 mA max.
Protected time duration: No limit

INPUT SPECIFICATIONS

DC Current: Input resistor incorporated

HART COMMUNICATION

Frequency band: 500 Hz – 10 kHz (within -10 dB)
Transmission gain: Approx. -3 dB (within 1 – 3 kHz)
measured with 250 Ω at output
Output load (loop impedance) 250 Ω ±10% is required for HART communication.
Communication directions: Bidirectional

INSTALLATION

Power Consumption
AC:
 Approx. 3.5 VA at 100 V
 Approx. 5.5 VA at 200 V
 Approx. 6.5 VA at 264 V
DC: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
  Supply output: ±3 % over voltage range
  Output signal: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM