ES-5154 Rev.3
M2EAXS
Super-mini Signal Conditioners with
Display Mini-M M2E Series
SELF-SYNCH ALARM
(PC programmable, dual or quad alarm trip)
Functions & Features
• Provides relay outputs at preset Self-Synch angle
• Quad or dual trip
• Front LCD display indicating values in scaled engineering unit range is used to program the module
• Adjustable deadband (hysteresis)
• ON delay time selectable
• Hi/Lo trip and energized/de-energized coil independently selectable for each setpoint
• Settable with front button
• Enclosed relays
• Relays can be powered by 200 V AC and 100 V DC
• High-density mounting on DIN rail
Typical Applications
• Annunciator
• Various alarm applications
MODEL: M2EAXS–[1]–[2][3]
ORDERING INFORMATION
• Code number: M2EAXS-[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. M2EAXS-2-K3/Q)
• Specify the specification for option code /Q
(e.g./C01/S01/SET)
INPUT
Self-synch signal
[1] OUTPUT
2:
4 points; N.O. or make contact
3:
4 points; N.C. or break contact
5:
2 points; SPDT or transfer contact
[2] POWER INPUT
AC Power
K3
: 100 – 120V AC
(Operational voltage range 85 - 132 V, 47 - 66 Hz)
L3
: 200 – 240V AC
(Operational voltage range 170 - 264 V, 47 - 66 Hz)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-5154)
Default setting will be used if not otherwise specified.
RELATED PRODUCTS
• M2EA configurator software (model: M2EACFG)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual (EM-5151) for the M2EA configurator for applicable cable types.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (gray)
Isolation
: input to L1 or L4 alarm output to L2 or L3 alarm output to power
(for output code 5, L3 alarm output and L4 alarm output is not available)
Configuration
: Program with front buttons or Via PC.
Programmable features include
: Refer to the parameter list.
Configurator connection
: 2.5 dia. miniature jack;
RS-232-C level
DISPLAY
Display functions
: Displays and sets measured range, engineering unit
Display size
: Approx. 15.6 × 20.8 mm (0.61” × 0.82”)
Number of pixels
: 68 × 95 (horizontal × vertical)
Character color
: Yellow (reversing display of the current value and the alarm setting value when alarm is tripped)
Display life
: Approx. 60000 hours
(Expected time for the Display brightness to be reduced to 50 % when the Display is used continuously with brightness setting 2 in 25 ℃)
Display type
: OEL display
Display digit
: Negative 5 digits, positive 6 digits (-99999 to 999999)
Decimal point position
: Selectable
INPUT SPECIFICATIONS
Measurement range
: 0 – 359.99° (deg)
Minimum span
: 60° (deg)
Input resistance
: 1 MΩ min.
Rated input voltage
: 30 – 90 V AC
OUTPUT SPECIFICATIONS
■
Quad Alarm
Relay rating
: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage
: 250 V AC or 125 V DC
Maximum switching power
: 120 VA or 30 W
Minimum load
: 5 V DC @ 10 mA
Mechanical life
: 5 × 10
7
cycles
■
DUAL ALARM
Relay rating
: 100 V AC @ 4 A (cos ø = 1)
120 V AC @ 4 A (cos ø = 1)
240 V AC @ 2 A (cos ø = 1)
30 V DC @ 4 A (resistive load)
Maximum switching voltage
: 250 V AC or 125 V DC
Maximum switching power
: 480 VA or 150 W
Minimum load
: 5 V DC @ 10 mA
Mechanical life
: 5 × 10
7
cycles
INSTALLATION
Power Consumption
•
AC
:
≤ 6 VA for 100 – 120 V
≤ 8 VA for 200 – 240 V
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 10 to 85 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: Approx. 200 g (0.44 lb)
PERFORMANCE in percentage of FS input
Accuracy (display accuracy, setting accuracy)
:
±0.2 % of span or ±0.5°(whichever is greater) ±1 digit.
See CALCULATION EXAMPLES OF OVERALL ACCURACY.
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time (Filter time constant: 0 sec.)
: ≤ 0.5 sec.
(0 – 100 % at 90 % setpoint)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (input to L1 or L4 alarm output to L2 or L3 alarm output to power to ground)
(for output code 5, L3 alarm output and L4 alarm output is not available)
CALCULATION EXAMPLES OF OVERALL ACCURACY
[Example] Input Span 60°
• Accuracy = Input (60°) × Accuracy (0.2 %) = 0.12°
0.12°< 0.5° thus
Accuracy = (0.5°) ÷ 60° × 100 = 0.83 % + 1 digit
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
L1 or L4 alarm output to L2 or L3 alarm output:
Basic insulation (300 V)
RoHS Directive
EXTERNAL VIEW
Refer to the operating manual (EM-5154-B) for detailed procedures.
PARAMETER LIST
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM