ES-5095 Rev.12
M2MNV
Super-mini Signal Conditioners Mini-M Series
ANALOG SWITCHING MODULE
Functions & Features
• Switches between two analog signal channels
• Switches/Distributes one voltage signal to two channels
Typical Applications
• Switching 1 – 5V DC signal: no contact failure that happens when using mechanical contacts for this purpose
• Switching low-speed pulse signals
MODEL: M2MNV-[1][2]-[3][4]
ORDERING INFORMATION
• Code number: M2MNV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M2MNV-11-M2/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Note: Must be used with its socket. NOT installable to a multi-unit installation base. (e.g. model: M2BS-16)
[1] SWITCHING CONTROL
1
: Interlocking switching control (single-pole contact)
2
: Independent switching control (double-pole contact)
[2] INPUT
1
: Current signal (no receiving resistor)
2
: Current signal (receiving resistor 50 Ω)
3
: Voltage signal
[3] POWER INPUT
AC Power
M
: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[4] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE or UKCA
/CE
: CE marking
/UK
: CE, UKCA marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
/C04
: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Switching
: Photo MOSFET relay
Isolation
: Signal channel to switching command contact to power
Power indicator LED
: Green light turns on when the power is supplied.
Status indicator LED 1
: Green light turns on when the signal channel 1 (A1-B1) is alive.
Status indicator LED 2
: Green light turns on when the signal channel 2 (A2-B1) is alive.
INPUT & OUTPUT
■ Signal Channels
Max. operational voltage range
: ±50 V DC (min. span 10 mV)
Max. operational current range
: ±50 mA DC (min. span 1 mA)
Max. operational frequency range
: 100 Hz
Receiving resistor
: 50 Ω incorporated (input code 2)
ON resistance
: ≤ 50 Ω per wire
(ON resistance of photo MOSFET relay)
■ Output
Current signal input (no receiving resistor)
:
Equal to the input signal
Current signal input (receiving resistor 50 Ω)
:
Voltage signal equal to [Current × 50 Ω]
Voltage signal input
: Equal to the input signal
■ Switching Command
: Relay or open collector
Contact detecting
: 5 V DC / 1 mA
Detecting levels
: ≤ 1 kΩ at ON / ≥ 10 kΩ at OFF
INSTALLATION
Power Consumption
•
AC
:
Approx. 3 VA at 100 V
Approx. 4 VA at 200 V
Approx. 5 VA at 264 V
•
DC
: Approx. 2 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 % (input code 2)
Temp. coefficient
: ±0.010 %/°C (±0.006 %/°F) (input code 2)
Switching response time
: ≤ 5 msec.
Leakage current at open circuit
: ≤ 1 μA
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric
strength
:
2000 V AC @1 minute
(switching command contact to power to ground)
2000 V AC @1 minute
(signal channel to power to ground)
1500 V AC @1 minute
(signal channel to switching command contact)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Signal channel or switching command contact to power: Reinforced insulation (300 V)
Signal channel to switching command contact: Basic insulation (300 V)
RoHS Directive
UK conformity (UKCA):
The UK legislations and designated standards are equivalent to the applicable EU directives.
(Refer to our website for more information about the legislations and designated standards.)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
SWITCHING OPERATIONS