Functions & Features
• Switches between two analog signal channels
• Switches/Distributes one voltage signal to two channels
Typical Applications
• Switching 1 – 5V DC signal: no contact failure that happens when using mechanical contacts for this purpose
• Switching low-speed pulse signals
 

MODEL: M2MNV-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: M2MNV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. M2MNV-11-M2/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)
Note: Must be used with its socket.  NOT installable to a multi-unit installation base. (e.g. model: M2BS-16)

[1] SWITCHING CONTROL

1: Interlocking switching control (single-pole contact)
2: Independent switching control (double-pole contact)

[2] INPUT

1: Current signal (no receiving resistor)
2: Current signal (receiving resistor 50 Ω)
3: Voltage signal

[3] POWER INPUT

AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz) 
(Select ‘/N’ for ‘Standards & Approvals’ code.)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[4] OPTIONS (multiple selections)

Standards & Approvals (must be specified)
/N: Without CE or UKCA
/CE: CE marking
/UK: CE, UKCA marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
/C04: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Switching: Photo MOSFET relay
Isolation: Signal channel to switching command contact to power
Power indicator LED: Green light turns on when the power is supplied.
Status indicator LED 1: Green light turns on when the signal channel 1 (A1-B1) is alive.
Status indicator LED 2: Green light turns on when the signal channel 2 (A2-B1) is alive.

INPUT & OUTPUT

■ Signal Channels
Max. operational voltage range: ±50 V DC (min. span 10 mV)
Max. operational current range: ±50 mA DC (min. span 1 mA)
Max. operational frequency range: 100 Hz
Receiving resistor: 50 Ω incorporated (input code 2)
ON resistance: ≤ 50 Ω per wire
(ON resistance of photo MOSFET relay)
■ Output
Current signal input (no receiving resistor)
:
Equal to the input signal
Current signal input (receiving resistor 50 Ω):
Voltage signal equal to [Current × 50 Ω]
Voltage signal input: Equal to the input signal
■ Switching Command: Relay or open collector
Contact detecting: 5 V DC / 1 mA
Detecting levels: ≤ 1 kΩ at ON / ≥ 10 kΩ at OFF

INSTALLATION

Power Consumption
AC:
 Approx. 3 VA at 100 V
 Approx. 4 VA at 200 V
 Approx. 5 VA at 264 V
DC: Approx. 2 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 % (input code 2)
Temp. coefficient: ±0.010 %/°C (±0.006 %/°F) (input code 2)
Switching response time: ≤ 5 msec.
Leakage current at open circuit: ≤ 1 μA
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
2000 V AC @1 minute
(switching command contact to power to ground)
2000 V AC @1 minute
(signal channel to power to ground)
1500 V AC @1 minute
(signal channel to switching command contact)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Installation Category II
  Pollution Degree 2
  Signal channel or switching command contact to power: Reinforced insulation (300 V)
  Signal channel to switching command contact: Basic insulation (300 V)
RoHS Directive
UK conformity (UKCA):
The UK legislations and designated standards are equivalent to the applicable EU directives.
(Refer to our website for more information about the legislations and designated standards.)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

SWITCHING OPERATIONS