ES-5166 Rev.2

M2PDU

Super-mini Signal Conditioners Mini-M Series

PULSE DIVIDER

Functions & Features
• Galvanically isolates and divides pulse rate signals
• Pulse division ratio is adjustable with the front switch, duty of the output pulse is 50%
• Various outputs (open collector, and voltage pulses)
• High-density mounting
Typical Applications
• Positive displacement flowmeters and turbine meters
• Dry contact signal produced at rotating machine

MODEL: M2PDU–[1][2][3]–[4][5]

ORDERING INFORMATION

• Code number: M2PDU-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
  (e.g. M2PDU-33N-M2/N/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] INPUT

1: Mechanical contact (max. 30 Hz)
2: Open collector (max. 100 kHz)
3: Voltage pulse (max. 100 kHz)
9: Clamp-on pulse sensor CLSP

[2] OUTPUT

1: Low frequency open collector (max. 30 Hz)
2: High frequency open collector (max. 100 kHz)
3: 5 V pulse (max. 100 kHz)
4: 12 V pulse (max. 100 kHz)
5: 24 V pulse (max. 100 kHz)

[3] OUTPUT LOGIC

N: The same as the input
R: Inverted

[4] POWER INPUT

AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[5] OPTIONS (multiple selections)

Standards & Approvals (must be specified)
/N: Without CE or UKCA
blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
/C04: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

• Clamp-on pulse sensor (model: CLSP)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Chattering protection: Filter provided for mechanical contact input
Input pulse sensing: DC coupled
■ Frequency Division
Duty ratio: 50%
(Duty of the output pulse is 50%)
When division is set, the duty ratio of the output signal is 50%.
However, if the division ratio is 1/1 (no division), the M2PDU outputs a signal equivalent to the input signal, so the duty of the output pulse may not be 50%.
(Example: When the duty of the input signal is 40% and the division ratio is set to 1/1 (no division), the duty of the output signal is approximately 40%.)
Setting division ratio: rotary switch (front)
In the range of 1/1 to 1/6400, division ratio can be set arbitrarily with the combinations of the switches.

INPUT SPECIFICATIONS

Excitation: 12 V DC @30 mA; shortcircuit protection
Duty ratio: 40 - 60 %
Open Collector
Maximum frequency
: 100 kHz
Pulse width time requirement: 5 μsec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 600 Ω / 1.8 V for ON, ≥ 100 kΩ / 3.5 V for OFF
Mechanical Contact
Maximum frequency
: 30 Hz
Pulse width time requirement: 10 msec. min. for ON and OFF
Sensing: Approx. 12 V DC @3 mA
ON/OFF level: ≤ 200 Ω / 0.6 V for ON, ≥ 100 kΩ / 2.5 V for OFF
Voltage Pulse
Maximum frequency: 100 kHz
Pulse width time requirement: 5 μsec. min. for high and low levels
Waveforms: Square or sine
Hi/Lo level: 2 – 50 V for high level; ≤1 V for low level
Input impedance: 10 kΩ min.
Clamp-on Pulse Sensor CLSP
Maximum frequency: 50 000 pulses/hour
ON/OFF level: ≤ 400 Ω / 1.3 V for ON, ≥ 200 kΩ / 12 V for OFF

OUTPUT SPECIFICATIONS

Low Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 30 Hz
Saturation voltage: 0.5 V DC
High Frequency Open Collector:
50 V DC @100 mA (resistive load)
Maximum frequency: 100 kHz
Saturation voltage: 0.5 V DC
Voltage Pulse
Maximum frequency: 100 kHz
High level: Rating (5, 12 or 24 V) ±10 %
Low level: ≤ 0.5V
Load resistance:
≥ 250 Ω for 5 V
≥ 600 Ω for 12 V
≥ 1200 Ω for 24 V

INSTALLATION

Power Consumption
AC:
 Approx. 4 VA at 100 V
 Approx. 5 VA at 200 V
 Approx. 6 VA at 264 V
DC: Approx. 2 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

EXTERNAL VIEW

OUTPUT LOGIC

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM