ES-5042 Rev.20
M2SED
Super-mini Signal Conditioners Mini-M Series
DC ALARM
(thumbwheel switch adjustment)
Functions & Features
• Provides SPDT relay outputs at preset DC input levels
• Dual (Hi / Lo) trip
• Thumbwheel switch setpoint adjustments
• Enclosed relays
• Relays can be powered 110 V DC
Typical Applications
• Annunciator
• Various alarm applications
MODEL: M2SED–[1][2]-[3][4]
ORDERING INFORMATION
• Code number: M2SED-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M2SED-613-P/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
Note: Must be used with its socket. NOT installable to a multi-unit installation base. (e.g. model: M2BS-16)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
4
: 0 – 10 V DC (Input resistance 1 MΩ min.)
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
[2] SETPOINT 1 OUTPUT / SETPOINT 2 OUTPUT
13
: Hi (coil energized at alarm)/
Lo (coil energized at alarm)
(/UL NOT available)
AB
: Hi (coil energized at alarm)/
Lo (coil energized at alarm)
(/UL available)
[3] POWER INPUT
AC Power
M2
: 100 – 240 V AC, 50 – 60 Hz
(Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
R2
: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
(Select ‘/N’ for ‘Standards & Approvals’ code.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[4] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE, UKCA or UL
/CE
: CE marking
/UK
: CE, UKCA marking
/UL
: UL approval, CE marking
(For /UL, "13" of setpoint output is NOT selectable)
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating (UL not available)
/C04
: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel (UL not available)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Setpoint adjustments
: Thumbwheel switches (front);
0 – 99 % independently; 1 % increments
Hysteresis (deadband)
: 1 ± 0.3 %
Front LEDs
: Red LED turns on when the coil is energized.
INPUT SPECIFICATIONS
■
DC Current
:
Shunt resistor attached to the input terminals (0.5 W)
OUTPUT SPECIFICATIONS
■
Relay Contact
Rated load:
100 V AC @5 A (cos ø = 1)
120 V AC @5 A (cos ø = 1)
240 V AC @2.5 A (cos ø = 1) (UL not available)
30 V DC @5 A (resistive load)
Maximum switching voltage (Note)
: 250 V AC or 125 V DC
Maximum switching power (Note)
: 600 VA or 150 W
Minimum load
: 5 V DC @10 mA
Mechanical life
: 5 × 10
7
cycles
(Note) The value indicate capacity of output relay in equipment. For EU, UK and UL, use within rated load.
INSTALLATION
•
AC
:
≤ 3 VA at 100 V
≤ 4 VA at 200 V
≤ 5 VA at 264 V
•
DC
: ≤ 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Installation Base (model: M2BS) is not adaptable.
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Setpoint accuracy
: ±0.5 %
Trip point repeatability
: ±0.05 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 0.5 ± 0.2 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
UK conformity (UKCA):
The UK legislations and designated standards are equivalent to the applicable EU directives.
(Refer to our website for more information about the legislations and designated standards.)
Approval
:
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
FRONT VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM