ES-7711 Rev.7
M3SYV
Super-space-saving Signal Conditioners
M3S-UNIT Series
ISOLATOR
Functions & Features
• Galvanically isolates the process instrumentation signals
• High-density mounting
MODEL: M3SYV–[1][2]–R[3]
ORDERING INFORMATION
• Code number: M3SYV-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. M3SYV-6A-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
D
: 0 – 20 mA DC (Input resistance 250 Ω)
DW
: -20 – +20 mA DC (Input resistance 250 Ω)
Voltage
4
: 0 – 10 V DC (Input resistance 1 MΩ min.)
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W
: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W
: -5 – +5 V DC (Input resistance 1 MΩ min.)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 550 Ω max.)
D
: 0 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 10 kΩ min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
GENERAL SPECIFICATIONS
Construction
: Small-sized front terminal structure
Connection
: Euro type connector terminal
Applicable wire size
: 0.2 to 2.5 mm
2
, stripped length 8 mm
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to output to power
Overrange output
: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment
: -2 to +2 % (front)
Span adjustment
: 98 to 102 % (front)
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
INSTALLATION
Power consumption
•
DC
: 1 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 100 g (0.22 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM