ES-7904 Rev.11
M6NPA
Screw Terminal Ultra-Slim Signal Conditioners M6N Series
FREQUENCY TRANSMITTER
Functions & Features
• 7.5-mm wide ultra-slim design
• Low profile allows the M6N module mounted in a 120-mm deep panel
• Converts the output from a pulse-type transducer into a standard process signal
• High-density mounting
• Power indicator LED
MODEL: M6NPA–[1][2]–R[3]
ORDERING INFORMATION
• Code number: M6NPA-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. M6NPA-CA-R/UL/Q)
• Frequency range (e.g. 0 – 1 kHz)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT
A1
: Open collector
A2
: Mechanical contact
C
: 5 V pulse (sensitivity 2 V)
D
: 24 V pulse (sensitivity 10 V)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 550 Ω max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
4W
: -10 – +10 V DC (Load resistance 20 kΩ min.)
5W
: -5 – +5 V DC (Load resistance 10 kΩ min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
Input and output
: M3 screw terminal (torque 0.5 N·m)
Power input
: Via the Installation Base (model: M6NBS)
or M3 screw terminal (torque 0.5 N·m)
Recommended solderless terminal
: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm
2
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: -2 to +2 % (front)
(Output code 4W, 5W: Adjustable at 0V.)
Span adjustment
: 98 to 102 % (front)
Chattering protection
: Filter provided for mechanical contact input
Power indicator LED
: Green LED turns on when the power is supplied.
■Recommended solderless terminal (unit: mm [inch])
INPUT SPECIFICATIONS
■
Open Collector
Frequency range
: 0 – 0.01 Hz through 100 kHz
Pulse width time requirement
: ≥ 4 µsec. for both H and L levels
Sensing voltage/current
: 2.5 V DC @1 mA (approx.)
Detecting levels
: ≤ 750 Ω/0.75 V for ON;
≥ 3 kΩ/1.6 V for OFF
■
Mechanical Contact
Frequency range
: 0 – 0.01 Hz through 30 Hz
Pulse width time requirement
: ≥ 10 msec. for both ON and OFF
Sensing voltage/current
: 2.5 V DC @1 mA (approx.)
Detecting levels
: ≤ 750 Ω/0.75 V for ON;
≥ 3 kΩ/1.6 V for OFF
■
Voltage Pulse
Frequency range
: 0 – 0.01 Hz through 100 kHz
Pulse width time requirement
: ≥ 4 µsec. for both H and L levels
Waveform
: Square or sine
Input impedance
: ≥ 10 kΩ
Max. voltage between input terminals
: ±50 V
Detecting H level
5 V pulse: ≥ 3 V
24 V pulse: ≥ 14 V
Detecting L level
5 V pulse: ≤ 1 V
24 V pulse: ≤ 6 V
OUTPUT SPECIFICATIONS
■ DC Current
: 2 – 20 mA DC (and 0 – 1 mA DC)
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 11 V max.
■
DC Voltage
: 0 – 10 V DC
Minimum span
: 1 V
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 1 V
INSTALLATION
Power consumption
: Approx. 0.5 W
Operating temperature
: -20 to +55°C (-4 to +131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Installation Base (model: M6NBS) or DIN rail
Weight
: 60 g (2.1 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: Max. 0.5 sec. + 1 pulse cycle (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
(With the cover open)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM