ES-7973 Rev.9
M6SDY
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
CURRENT LOOP SUPPLY
Functions & Features
• Maintenance-free tension clamp connection
• 5.9-mm wide ultra-slim design
• Low profile allows the M6S module mounted in a 120-mm deep panel
• Powers a two-wire transmitter and galvanically isolates its output signal
• High-density mounting
• Power indicator LED
MODEL: M6SDY–[1]–R[2]
ORDERING INFORMATION
• Code number: M6SDY-[1]-R[2]
Specify a code from below for each of [1] and [2].
(e.g. M6SDY-A-R/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
INPUT
Current
4 – 20 mA DC (Input resistance 249.5 Ω)
[1] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 550 Ω max.)
Voltage
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
Input and output
: Tension clamp
Power input
: Via the Installation Base (model: M6SBS)
or Tension clamp
Applicable wire size
: 0.2 to 2.5 mm
2
, stripped length 8 mm
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: -2 to +2 % (front)
Span adjustment
: 98 to 102 % (front)
Power indicator LED
: Green LED turns on when the power is supplied.
SUPPLY OUTPUT
(across the terminals 3 – 4)
Output voltage
: 24 – 30 V DC with no load
18 V DC min. at 20 mA
Current rating
: ≤ 22 mA DC
•
Shortcircuit Protection
Current limited
: 45 mA max.
Protected time duration
: No limit
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
INSTALLATION
Power consumption
: Approx. 1 W (1.1 W for UL approval)
Operating temperature
: -20 to +55°C (-4 to +131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Installation Base (model: M6SBS) or DIN rail
Weight
: 60 g (2.1 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F)
Response time
: ≤ 100 msec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
(With the cover open)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM