ES-7994 Rev.6

M6SVF

Tension-Clamp Ultra-Slim Signal Conditioners M6S Series

SIGNAL TRANSMITTER

(high-accuracy, ultra-high speed response 30 μsec.)
Functions & Features
• Maintenance-free tension clamp connection
• 5.9-mm wide ultra-slim design
• Low profile allows the M6S module mounted in a 120-mm deep panel
• Galvanically isolates process instrumentation signals
• 30-microsecond response
• Frequency characteristics 12 kHz (-3 dB)
• High-density mounting
• Power indicator LED
Typical Applications
• Isolation for a vibration analyzing system
• Isolation for Discharge/Charge tester

MODEL: M6SVF–[1]4W–R[2]

ORDERING INFORMATION

• Code number:  M6SVF-[1]4W-R[2]
Specify a code from below for each of [1] and [2].
  (e.g. M6SVF-04W-R/Q)
• Special input range (For code 0: e.g. -164 – +164 mV DC)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] INPUT

Voltage
2W: -100 – +100 mV DC (Input resistance 1 MΩ min.)
4W: -10 – +10 V DC (Input resistance 1 MΩ min.)
5W: -5 – +5 V DC (Input resistance 1 MΩ min.)
8W: -20 – +20 V DC (Input resistance 1 MΩ min.)
0: Specify voltage
(Select input range as indicated below.  Input resistance 1 MΩ min.)
-20 – +20 mV DC
-24 – +24 mV DC
-40 – +40 mV DC
-85 – +85 mV DC
-164 – +164 mV DC
-200 – +200 mV DC
-15 – +15 V DC
-25 – +25 V DC
-55 – +55 V DC
-60 – +60 V DC

OUTPUT

Voltage
4W: -10 – +10 V DC (Load resistance 2000 Ω min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

GENERAL SPECIFICATIONS

Connection
Input and output: Tension clamp
Power input: Via the Installation Base (model: M6SBS)
or Tension clamp
Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange input: -5 to +105 %
Zero adjustment: -1 to +1 % (front)
Span adjustment: 99 to 101 % (front)
Power indicator LED: Green LED turns on when the power is supplied.

INPUT SPECIFICATIONS

Input resistance: 1 MΩ min. (3 kΩ min. at power loss)

OUTPUT SPECIFICATIONS

Parallel load capacitance: Max. 2000 pF

INSTALLATION

Power consumption: Approx. 0.6 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6SBS) or DIN rail
Weight: 60 g (2.1 oz)

PERFORMANCE in percentage of span

Accuracy: ±0.01 %
Temp. coefficient: ±0.005 %/°C (±0.003 %/°F)
Frequency characteristics: 12 kHz, -3 dB
Response time: ≤ 30 µsec. (0 – 90 %)
Line voltage effect: ±0.01 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

(With the cover open)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM