ES-7971 Rev.9
M6SYV
Tension-Clamp Ultra-Slim Signal Conditioners M6S Series
ISOLATOR
Functions & Features
• Maintenance-free tension clamp connection
• 5.9-mm wide ultra-slim design
• Low profile allows the M6S module mounted in a 120-mm deep panel
• Galvanically isolates process instrumentation signals
• High-density mounting
• Power indicator LED
MODEL: M6SYV-[1][2]-[3][4]
ORDERING INFORMATION
• Code number: M6SYV-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M6SYV-4W4W-R/K/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT / [2] OUTPUT
AA
: 4 - 20 mA DC (Input resistance 50 Ω)
/ 4 - 20 mA DC (Load resistance 550 Ω max.)
A6
: 4 - 20 mA DC (Input resistance 50 Ω)
/ 1 - 5 V DC (Load resistance 5000 Ω min.)
6A
: 1 – 5 V DC (Input resistance 1 MΩ min.)
/ 4 - 20 mA DC (Load resistance 550 Ω max.)
66
: 1 - 5 V DC (Input resistance 1 MΩ min.)
/ 1 - 5 V DC (Load resistance 5000 Ω min.)
4W4W
: -10 - +10 V DC (Input resistance 1 MΩ min.)
/ -10 - +10 V DC (Load resistance 20 kΩ min.)
[3] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 90 – 264 V,
47 – 66 Hz)
(UL not available)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank
: Standard (≤ 0.5 sec.)
/K
: Fast Response (Approx. 3.5 msec. voltage output;
Approx. 25 msec. current output)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
Input and output
: Tension clamp
Power input
: Via the Installation Base (model: M6SBS)
(not available for AC power input)
or Tension clamp
Applicable wire size
: 0.2 to 2.5 mm
2
, stripped length 8 mm
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: -2 to +2 % (front)
(Output code 4W: Adjustable at 0 V.)
Span adjustment
: 98 to 102 % (front)
Power indicator LED
: Green LED turns on when the power is supplied.
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
INSTALLATION
Power Consumption
•
AC
: Max. 2 VA
•
DC
: Approx. 0.45 W
Operating temperature
: -20 to +55°C (-4 to +131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Installation Base (model: M6SBS) or DIN rail
Weight
: 60 g (2.1 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Installation Category II
Pollution Degree 2
Input or output to power: Reinforced insulation (300 V)
Input to output: Basic insulation (300 V)
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
EXTERNAL VIEW
(With the cover open)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM