ES-5396 Rev.2
M80YV
Super-mini Signal Conditioners M80 Series
SIGNAL CONVERTER
Functions & Features
• Converts DC input into isolated standardized process signal
• Isolates between analog input channels of a PLC
• Achieves space-saving and easy maintenance with Multi-channel Installation Base
MODEL: M80YV-[1]6-R
ORDERING INFORMATION
• Code number: M80BW-[1]6-R
Specify a code from below for [1].
(e.g. M80BW-66-R)
[1] INPUT
Current
A
: 4 – 20 mA DC (Input resistance 250 Ω)
D
: 0 – 20 mA DC (Input resistance 250 Ω)
Voltage
5
: 0 – 5 V DC (Input resistance 1 MΩ min.)
6
: 1 – 5 V DC (Input resistance 1 MΩ min.)
4W
: -10 – +10 V DC (Input resistance 1 MΩ min.)
OUTPUT
Voltage
6
: 1 – 5 V DC (Load resistance 10 kΩ min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
RELATED PRODUCTS
• Installation Base (model: M80BSx)
This unit must be mounted on a dedicated base.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Housing material
: Flame-resistant resin (gray)
Power supply
: Via the Installation Base terminals
(model: M80BSx)
Isolation
: Input to output to power
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
■
DC Voltage
Input resistance
: 1 MΩ min. (10 kΩ min. in power failure)
INSTALLATION
Current consumption
: Approx. 50 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 5 to 95 %RH (non-condensing)
Mounting
: Multi-channnel Installation Base (model: M80BSx)
Weight
: 20 g (0.71 oz)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: ≤ 15 msec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM