ES-5495 Rev.17
M8BS2
Dual Output Super-mini Signal Conditioners Pico-M Series
INSTALLATION BASE (for network interface)
Functions & Features
• Holding up to 16 modules of Pico-M series signal conditioners
• Direct connection to various networks via the 61-Unit Analog Input Modules mounted on the base
• Power supplied through printed wiring on the base
• Saving wiring work within an instrumentational panel
MODEL: M8BS2–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: M8BS2-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. M8BS2-161-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] CAPACITY
04
: 4 positions
08
: 8 positions
16
: 16 positions
[2] I/O TYPE
1
: Input (Select 1 – 5V for Output 1.)
2
: Output (Select model M8YVx with 1 – 5V input.)
3
: Output (Select model M8YSx with 1 – 5V input.)
4
: Input/Output
(Input channel 8 points: Select 1 - 5 V for Output 1.)
(Output channel 8 points: Select model M8YVx with 1 - 5V input.)
(Specify capacity code 16.)
(Only 61C-163-R is available for related products.)
(CE not available)
[3] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 63 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
Only solder side of the main PWB is coated.
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Analog I/O Module (model: 61x)
Specify power input code 'R' (24V DC).
For Input/Output type, specify 61C-163-R.
PACKAGE INCLUDES...
• Ferrite core (model: GRFC-10)(Kitagawa Industries): 1 pce. (Only for M2 power)
GENERAL SPECIFICATIONS
Capacity
: 4, 8 or 16 positions
Connection
Power input
M2
: M3 screw terminals (torque 0.8 N·m)
R
: M3.5 screw terminals (torque 0.8 N·m)
Input and output
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: Input to output 1 to output 2 to power to FG
Power indicator LED
: ON with normal voltage level
INSTALLATION
Power Consumption
•
AC
: 130 VA min.
•
DC
: 2.5 A min.
Operating temperature
: 0 to 55°C (32 to 131°F)
0 to 50°C (32 to 122°F) for AC power
Operating humidity
: 30 to 90 %RH (non- condensing)
30 to 85 %RH for AC power
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface
Weight
AC power
:
1.0 kg (2.2 lb) (4 positions)
1.2 kg (2.6 lb) (8 positions)
2.5 kg (5.5 lb) (16 positions)
DC power
:
0.6 kg (1.3 lb) (4 positions)
0.8 kg (1.8 lb) (8 positions)
2.0 kg (4.4 lb) (16 positions)
PERFORMANCE
Insulation resistance
Input use
: ≥ 100 MΩ with 500 V DC
(input to output 2 to power to FG)
Output use
: ≥ 100 MΩ with 500 V DC
(output 1 to output 2 to power to FG)
Input/Output use
: ≥ 100 MΩ with 500 V DC
(Input(input side) to Output 2(input side) to Output 1(output side) to Output 2(output side) to power to FG)
Dielectric strength
•
Input use
DC power
:
1500 V AC @1 minute (input to output 2 or power to FG)
500 V AC @1 minute (output 2 to power)
AC power
:
1500 V AC @1 minute (input to output 2 or power)
1500 V AC @1 minute (input to FG)
500 V AC @1 minute (output 2 to power to FG)
•
Output use (M8YVx)
DC power
:
1500 V AC @1 minute (output 1 or output 2 or power to FG)
500 V AC @1 minute (output 1 to output 2 to power)
AC power
:
1500 V AC @1 minute (input to output 1 or output 2 or power)
1500 V AC @1 minute (input to FG)
500 V AC @1 minute (output 1 to output 2 to power to FG)
•
Output use (M8YSx)
DC power
:
1500 V AC @1 minute (input or output or power to FG)
500 V AC @1 minute (input to power)
AC power
:
1500 V AC @1 minute (output to input or power)
1000 V AC @1 minute (output to FG)
500 V AC @1 minute (input to power to FG)
•
Input/Output use
DC power
:
1500 V AC @1 minute (Input(input side) to Output 2(input side) or Output 1(output side) or Output 2(output side) or power to FG)
500 V AC @1 minute (Output 2(input side) to Output 1(output side) to Output 2(output side) to power)
AC power
:
1500 V AC @1 minute (Input(input side) to Output 2(input side) or Output 1(output side) or Output 2(output side) or power)
1500 V AC @1 minute (Input(input side) to FG)
500 V AC @1 minute (Output 2(input side) to Output 1(output side) to Output 2(output side)to power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
The AC power unit conforms with the following standards:
EN 50178
Installation Category II
Pollution Degree 2
Max. operating voltage 300 V
RoHS Directive
MOUNTING REQUIREMENTS unit: mm (inch)
■ M8BS2-04x
■ M8BS2-08x
■ M8BS2-16x
CONNECTION DIAGRAM
■ INPUT/OUTPUT TYPE
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
■ M8BS2-041-M2
■ M8BS2-041-R
■ M8BS2-042-M2
■ M8BS2-042-R
■ M8BS2-043-M2
■ M8BS2-043-R
■ M8BS2-081-M2
■ M8BS2-081-R
■ M8BS2-082-M2
■ M8BS2-082-R
■ M8BS2-083-M2
■ M8BS2-083-R
■ M8BS2-161-M2
■ M8BS2-161-R
■ M8BS2-162-M2
■ M8BS2-162-R
■ M8BS2-163-M2
■ M8BS2-163-R
■M8BS2-164-M2
■M8BS2-164-R