Functions & Features
• Converts an alternating current into a standard process signal
• Easy-to-install clamp-on type current sensor without needing a current transformer
• Clamp-on current sensor included
• Wide input range from 10 A up to 600 A
• True RMS sensing
• Space-saving, easy-to-maintain, multi-channel installation base
Typical Applications
• Centralized monitoring and control of motors at a supervisory panel
• Monitoring abnormal load current at motors to detect pump malfunctions
MODEL: M8CTC-[1][2][3]-R[4]
ORDERING INFORMATION
• Code number: M8CTC-[1][2][3]-R[4]
Specify a code from below for each of [1] through [4].
(e.g. M8CTC-1506A-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/V01)
[1] SENSOR
1
: Leadwire type CLSA
2
: Screw terminal type CLSB
[2] INPUT
10
: 0 – 10 A AC
15
: 0 – 15 A AC
20
: 0 – 20 A AC
30
: 0 – 30 A AC
40
: 0 – 40 A AC
50
: 0 – 50 A AC
60
: 0 – 60 A AC
75
: 0 – 75 A AC
100
: 0 – 100 A AC
125
: 0 – 125 A AC
150
: 0 – 150 A AC
175
: 0 – 175 A AC
200
: 0 – 200 A AC
225
: 0 – 225 A AC
250
: 0 – 250 A AC
300
: 0 – 300 A AC
350
: 0 – 350 A AC
400
: 0 – 400 A AC
500
: 0 – 500 A AC
600
: 0 – 600 A AC (Not selectable with the sensor type
code 1 'Leadwire type CLSA')
[3] OUTPUT 1 / OUTPUT 2
6A
: 1 – 5 V DC (Load resistance 2500 Ω min.)
/ 4 – 20 mA DC (Load resistance 300 Ω max.)
44
: 0 – 10 V DC (Load Resistance 5000 Ω min.)
/ 0 – 10 V DC (Load Resistance 5000 Ω min.)
55
: 0 – 5 V DC (Load resistance 2500 Ω min.)
/ 0 – 5 V DC (Load resistance 2500 Ω min.)
66
: 1 – 5 V DC (Load resistance 2500 Ω min.)
/ 1 – 5 V DC (Load resistance 2500 Ω min.)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
ADJUSTMENT
/V01
: Multi-turn fine adjustment
RELATED PRODUCTS
• Installation Base or Single Mount Base Socket (model: M8BSx)
This unit must be mounted on dedicated base or socket.
ACCESSORIES
The clamp-on current sensor is included in the product package.
■
CLAMP-ON CURRENT SENSOR (leadwire type CLSA)
•
0 – 10 A through 0 – 75 A Use
Sensor model No.
: CLSA-08
Sensor cable model No.
: CLSA-08C-30
Applicable cable diameter
: Max. 10.0
Sensor leadwire
: AWG 22
Weight
: 45 g (1.6 oz)
•
0 – 100 A Use
Sensor model No.
: CLSA-12
Sensor cable model No.
: CLSA-08C-30
Applicable cable diameter
: Max. 16.0
Sensor leadwire
: AWG 22
Weight
: 70 g (2.5 oz)
•
0 – 125 A through 0 – 300 A Use
Sensor model No.
: CLSA-30
Applicable cable diameter: Max
. 24.0
Sensor leadwire
: AWG 18, 200 mm
Weight
: 200 g (7.1 oz)
•
0 – 350 A through 0 – 500 A Use
Sensor model No.
: CLSA-50
Applicable cable diameter
: Max. 36.0
Sensor leadwire
: AWG 18, 200 mm
Weight
: 300 g (10.6 oz)
■
CLAMP-ON CURRENT SENSOR (screw terminal type CLSB)
Connection
: M3 screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Output wiring:
Use AWG22 or thicker wires for the output. Twist the paired wires, extendable up to 30 meters.
•
0 – 10 A through 0 – 50 A Use
Sensor model No.
: CLSB-05
Applicable cable diameter
: Max. 10.0
Weight
: 45 g (1.6 oz)
•
0 – 60 A through 0 – 100 A Use
Sensor model No.
: CLSB-10
Applicable cable diameter
: Max. 16.0
Weight
: 80 g (2.8 oz)
•
0 – 125 A through 0 – 200 A Use
Sensor model No.
: CLSB-20
Applicable cable diameter
: Max. 24.0
Weight
: 200 g (7.1 oz)
•
0 – 225 A through 0 – 400 A Use
Sensor model No.
: CLSB-40
Applicable cable diameter
: Max. 35.0
Weight
: 300 g (10.6 oz)
•
0 – 500 A through 0 – 600 A Use
Sensor model No.
: CLSB-60
Applicable cable diameter
: Max. 35.0
Weight
: 360 g (12.7 oz)
Note 1: The output values may vary depending on the accuracy of engagement at the clamp connection.
Note 2: The sensor is detachable up to 100 times (approx.).
Note 3: The sensor’s mechanical construction may cause it to generate resonance sound. However, it does not affect the performance of the sensor.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Mounting screw
: M3 screw (torque 0.3 N·m)
Housing material
: Flame-resistant resin (black)
Power supply
: Via the Installation Base terminals
(model: M8BSx)
Isolation
: Sensor core to sensor output or input to output 1 to output 2 to power
Input waveform
RMS sensing
: Up to 15 % of 3rd harmonic content
Zero adjustment
: -2 to +2 % (front)
Span adjustment
: 98 to 102 % (front)
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz
Overload capacity
CLSA - 08
: 120 A continuous
CLSA - 12
: 300 A continuous
CLSA - 30
: 360 A continuous
CLSA - 50
: 600 A continuous
CLSB - 05
: 100 A continuous
CLSB - 10
: 200 A continuous
CLSB - 20
: 300 A continuous
CLSB - 40
: 600 A continuous
CLSB - 60
: 720 A continuous
Operational range
: 0 – 120 % of rating
Be sure that the input voltage is of 440 V or less.
INSTALLATION
Current consumption
: Approx. 30 mA (50 mA for current output)
Operating temperature
: 0 to 55°C (32 to 131°F)
Operating humidity
: 30 to 95 %RH (non-condensing)
Mounting
: Installation Base (model: M8BSx)
Weight
: 70 g (2.5 oz)
PERFORMANCE in percentage of span
Accuracy
: ±1 %
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Response time
: ≤ 0.25 sec. (0 – 90 %)
Ripple
: 0.5 %p-p max.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @1 minute (input to output 1 or output 2 or power to ground)
500 V AC @1 minute(output 1 to output 2 to power)
1000 V AC @1 minute(sensor core to sensor output)
SWC test
: ANSI/IEEE-C37.90.1-1989
EXTERNAL DIMENSIONS unit: mm [inch]
■ Sensor model No.: CLSA-08
■ Sensor model No.: CLSA-12
■ Sensor model No.: CLSA-30
■ Sensor model No.: CLSA-50
■ Sensor model No.: CLSB-05
■ Sensor model No.: CLSB-10
■ Sensor model No.: CLSB-20
■ Sensor model No.: CLSB-40
■ Sensor model No.: CLSB-60
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM