ES-8160 Rev.4

MATPH

Lightning Surge Protectors for
Electronics Equipment M-RESTER

SURGE PROTECTOR FOR PHOTOVOLTAIC SYSTEM

(750V DC,1000V DC USE)
Functions & Features
• Surge protection for photovoltaic array and power conditioner.
• High discharge current capacity 20 kA
• Degraded head element is automatically separated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status.
• Breakdown of the surge protector remotely detected with the alarm output
• Photovoltaic system's resistance to earth is measurable without removing the SPD due to spark gap employed between line and earth.
 

MODEL: MATPH–[1]M[2]

ORDERING INFORMATION

• Code number: MATPH-[1]M[2]
Specify a code from below for each of [1] and [2].
  (e.g.MATPH-1000MA)

[1] OPERATIONAL VOLTAGE

750: 750 V DC
1000: 1000 V DC

MAXIMUM DISCHARGE CURRENT

M: 20kA (8/20 μsec.)

[2] ALARM OUTPUT

A: With
Y: Without

GENERAL SPECIFICATIONS

Construction: Standalone; terminal access at the front
Degree of protection: IP20 (If the solderless terminals are covered with insulation tubes.)
Surge protection type: One-port combination type SPD
Connection
  Line: M5 screw terminal (torque: 2.5 N·m)
  Alarm output: Tension clamp
Applicable wire size
 Line: See the drawing below.
 Alarm output: 0.13 to 1.5 mm2, stripped length 8 mm
Screw terminal
 Line
: Nickel-plated steel
 Alarm output: Tin-plated copper alloy
Housing material: Flame-resistant resin (black)
Alarm output: Trips when the thermal breaker operates. (N.C. contact)
Rated load:
250 V AC @50 mA (resistive load)
24 V DC @50 mA (resistive load)
Safety function: Thermal breaker incorporated
Monitor LED: Green LED turns on during normal conditions (100 V DC to operational votage), and turns off during failure condition, power off and the thermal breaker operating.

INSTALLATION

Operating temperature: -25 to +80°C (-13 to +176°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN Rail
Weight: 200 g (0.44 lb)

PERFORMANCE

Max. continuous operating voltage (Uc, Line to line):
 750 V DC for MATPH-750
 1000 V DC for MATPH-1000
Discharge voltage (Line to earth): 500 V DC
Voltage protection level (Up):
• MATPH-750
 Line to line: 2.5 kV (@In) 
 Line to earth: 1.8 kV (@In)
• MATPH-1000
 Line to line: 3.3 kV (@In)
 Line to earth:  2.1 kV  (@In)
Maximum discharge current (Imax): 20 kA (8/ 20 μs)
Nominal discharge current (In): 10 kA (8/ 20 μs)
Response time:
 Line to line: ≤ 4 nsec.
 Line to earth: ≤ 20 nsec.
Leakage current: ≤ 1 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC (line to alarm output)
Dielectric strength: 2000 V AC @ 1 minute (line to alarm output)
Surge protection: IEC 61643-1 Class II
                             EN 61643-11 Class II

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
Low Voltage Directive
  EN 61643-11
RoHS Directive

CONNECTION EXAMPLES

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY