ES-8138 Rev.4
MDCAT-NC
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR CC-Link IE Field Network
Functions & Features
• Recommended for CC-Link IE Field Network
• LAN cable’s shield wire can be floating or grounding by a shortcircuit bar
• DIN rail mounting
• Grounding with M3 screw terminal or via DIN rail
MODEL: MDCAT-NC-5E
ORDERING INFORMATION
• Code number: MDCAT-NC-5E
CABLE CATEGORY
5E
: CAT5e
PACKAGE INCLUDES...
LAN cable connected to the protected device
(Compatible cable with CC-Link IE Field Network, 0.5 meters)
APPLICABLE NETWORK
Applicable network
: CC-Link IE Field Network
Applicable cable
: Compatible cable wiith CC-Link IE Field Network
GENERAL SPECIFICATIONS
Connection
Network
: RJ-45 modular jack
Grounding
: M3 screw terminal (torque 0.6 N·m)
or via DIN rail
Screw terminal
: Nickel-plated brass
Housing material
: Flame-resistant resin (black)
INSTALLATION
Operating temperature:
-25 to +85°C (-13 to +185°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Mounting
: DIN Rail (TH35-7.5, 1-mm-thick)
When this unit is earthed via a DIN rail, use a steel or copper rail. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Weight
: 150 g (0.33 lb)
PERFORMANCE
Max. continuous operating voltage
(Uc)
:
Line to line 1: ±6 V
Line to line 2: ±58 V
Line to earth: ±150 V
Voltage protection level (Up)
:
Line to line 1: ±15 V (@2 kV, 1.2/50 μsec.)
Line to line 2: ±100 V (@2 kV, 1.2/50 μsec.)
Line to earth: ±600 V (@4 kV, 1.2/50 μsec.)
Response time
:
Line to line 1: 4 nsec.
Line to line 2: 4 nsec.
Line to earth: 20 nsec.
Leakage current @Uc
:
Line to line 1: 25 μA
Line to line 2: 5 μA
Line to earth: 5 μA
Max. discharge current (Imax)
Line to line 1: 100 A (8/20 μsec.)
Line to line 2: 100 A (8/20 μsec.)
Line to earth: 10 kA (8/20 μsec.)
Nominal current (I
N
)
: 1 A
Series resistance
: approx. 0 Ω
Transmission performance
: TIA/EIA-568-B.2 CAT5e
Surge protection
: IEC 61643-21 Categories C1, C2
Note: "Line to line 1" stands for electrodes 1 – 2, 3 – 6, 4 – 5 and 7 – 8, "line to line 2" stands for electrodes 1 or 2 – 3 or 6 and 4 or 5 – 7 or 8 of RJ-45 Modular jack.
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
CONNECTION EXAMPLES
• Install the lightning surge protectors in places where it is considered that lightning surge may enter (where panels/cabinets are greatly separated, such as outdoor wiring).
• The maximum number of surge protectors that can be installed between devices is two (2). Take into account insertion loss 1 dB per surge protector as a rough indication.
• Refer to "CC-Link IE Field Network Cable Installation Manual” issued by CC-Link Partner Association for details.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY