ES-8197 Rev.1
MDCAT-SPE-A
Lightning Surge Protectors for
Electronics Equipment M-RESTER
LIGHTNING SURGE PROTECTOR FOR SINGLE PAIR ETHERNET
(PoDL, life monitor)
Functions & Features
• Designed specifically for Ethernet network
• Conforms with PoDL
• LAN cable’s shield wire can be floating or grounding by a shortcircuit bar
• Pressing CHK (Check) button confirms with LEDs the life span of the surge protect device
• Compact and light weight
• DIN rail mounting
MODEL: MDCAT-SPE-A-[1]
ORDERING INFORMATION
• Code number: MDCAT-SPE-A-[1]
Specify a code from below for [1].
(e.g. MDCAT-SPE-A/DR/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS (multiple selections)
Single mount DIN rail
blank
: Without
/DR
: With single mount DIN rail
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
• When this unit is earthed via a DIN rail, use a steel or copper rail. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
• Single mount DIN rail for option code ‘/DR’ is made of aluminum. Connect to ground with ground terminal when this DIN rail is used.
APPLICABLE NETWORK
10 BASE-T1L
: IEEE 802.3cg
PoDL
: IEEE802.3bu
GENERAL SPECIFICATIONS
Connection
Network
: Euro type connector terminal
(Applicable wire size: 0.2 - 2.5 mm
2
)
Grounding
: M3 screw terminal (torque 0.6 N·m)
or via DIN rail
Screw terminal
: Nickel-plated brass
DIN rail material
: Aluminum
Housing material
: Flame-resistant resin (black)
Indicators:
Activated by CHK (Check) button, see the status table shown below.
•BAT: Green LED
•ALM: Red LED
Life time judged:
When the number of discharges of the discharge element reaches the expected life span.
CHK button:
Push button; momentary
Battery
: Lithium; No recharge or replacement available.
Battery life
: 10 years (when used ≤ 2 minutes/month)
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 10 to 95 % RH (non-condensing)
Mounting
: DIN Rail (TH35-7.5, 1-mm-thick)
Weight
: 80 g (2.8 oz)
PERFORMANCE
Max. continuous operating voltage (Uc)
· ± 60 V
Voltage protection level
· ≤ 600 V (line to earth)
Leakage current (@Uc)
· 5 μA
Nominal current (I
N
):
1.5 A
Impulse durability
· C2 (8/20 μsec.): 5 kA
· D1 (10/350 μsec.): 1 kA
Series resistance
: approx. 0 Ω
Insertion loss
: ≤ 0.3 dB (DC - 10 MHz)
Surge protection: IEC 61643-21 Categories C2, D1
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
CONNECTION EXAMPLES
EXTERNAL DIMENSIONS unit: mm [inch]