ES-8117 Rev.13

MDP-EC

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR EC-CABLE USE

Functions & Features
• Designed specifically for the 32-point
Transmission System EC-CABLE
• Protects the transmitter model ECT and the receiver ECR from lightning surges entering through the twisted-pair cables connecting the both modules
• Applicable to transmission systems by current loops
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging the protector element

MODEL: MDP–EC[1]

ORDERING INFORMATION

• Code number: MDP-EC[1]
Specify a code from below for [1].
  (e.g. MDP-EC/A33/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS (multiple selections)

DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight:
120 g (0.26 lb), standard
145 g (0.32 lb), with DIN rail mounting adapter

PERFORMANCE

Max. continuous operating voltage (Uc): 
 Line to line: ±12 V  
 Line to earth: ±500 V
Voltage protection level (Up):
• @ 1 kV (100 A)
 Line to line: ±25 V 
 Line to earth:  ±650 V
• @ 2 kV (1 kA) 
 Line to line: ±30 V
 Line to earth: ±800 V
Response time: ≤ 0.1 μsec.
Leakage current:
 Line to line: ≤ 10 μA @ ±12 V DC
 Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
Nominal current (IN): 100 mA
Internal series resistance: 20 Ω ±10 % (including return)
Capacitance @ 1 MHz:
 Line to line:  ≤ 1000 pF
 Line to earth: ≤ 100 pF
Surge protection: IEC 61643-21 Categories C1, C2

CONNECTION EXAMPLES

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM